32b
Service parameter(s) 12
12 Boost
Circuit
Setting range
I
0 ... 99%
Shortens the heating-up period by increasing the desired flow
temperature by the percentage you set.
Set the percentage at which you want the desired
flow temperature increased temporarily.
In order to shorten the heating-up period after a setback
temperature period, the desired flow temperature can be
increased temporarily (max. 1 hour). At optimizing the boost
is active in the optimization period (line 14).
If a room temperature sensor or an ECA 60 / 61 / 62 / 63 is
connected, the boost stops when the room temperature has
been reached.
The boost also stops at the end of an optimizing period.
Boost is only active during heating operation.
The grey
side of the
ECL Card
Factory setting
0%
Service parameter(s) 14
14 Optimizing time constant
Circuit
Setting range
I
OFF / 10 ... 59
Optimizes the start and stop times for the comfort temperature
period to obtain the best comfort at the lowest energy
consumption. The lower the outdoor temperature, the earlier the
heating cut-in.
Adjust the optimizing time constant. The value
consists of a two digit number.
The two digits have the following meaning:
Digit 1
Heat accumulation of
1
2
3
4
5
Digit 2
Dimensioning
temperature
0
1
5
9
OFF: No optimization. The heating starts and
stops at the times set in the schedule.
Dimensioning temperature:
The lowest outdoor temperature (usually determined by your
system designer in connection with the design of the heating
system) at which the heating system can maintain the designed
room temperature.
32c
Factory setting
System type
the building
light
Radiator
systems
medium
heavy
medium
Floor heating
systems
heavy
Capacity
- 50 °C
large
- 45 °C
- 25 °C
normal
- 5 °C
small
The grey
side of the
ECL Card
45