Foundation Fieldbus Communication; Option Modules; Alarm Module - Siemens SIPART PS2 Compact Operating Instructions

Electropneumatic positioners
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
PC parameter assignment
software

FOUNDATION Fieldbus communication

Communication group and
class
Function blocks
Execution times of the blocks
Physical layer profile
FF registration
Device address

Option modules

Alarm module

Alarm module
3 binary output circuits
● Alarm output A1: Terminals 31 and 32
● Alarm output A2: Terminals 41 and 42
● Fault message output: Terminals 51 and 52
● Auxiliary voltage U
H
● Signal status
High (not addressed)
Low *) (addressed)
*) The status is also Low if the
basic device is faulty or without
a power supply.
● For connecting to circuits with the
following peak values
● Effective inner capacitance C
● Effective inner inductance L
1 binary input circuit
● Binary input BE2: Terminals 11 and 12, terminals 21 and 22 (jumper)
● Galvanically connected with the
basic device
Signal status 0
Signal status 1
SIPART PS2 (6DR5...)
A5E03436620-01, 03/2011
SIMATIC PDM; supports all device objects. The software is not included in the scope of
delivery.
According to the technical specification of the Fieldbus Foundation for H1 communication
Group 3, Class 31PS (Publisher Subscriber)
1 resource block (RB2)
1 analog output function block (AO)
1 PID function block (PID)
1 transducer block (standard advanced positioner valve)
AO: 60 ms
PID: 80 ms
123, 511
Tested with ITK 5.0
22 (when delivered)
Without Ex protection/
with Ex protection Ex d
6DR4004-8A
≤ 35 V
Conductive, R = 1 kΩ,
+3/-1% *)
Deactivated, I
< 60 µA
R
*) When using in the
flameproof enclosure, the
current consumption must
be restricted to 10 mA per
output.
-
-
i
-
i
With Ex protection Ex ia
6DR4004-6A
-
≥ 2.1 mA
≤ 1.2 mA
Switching thresholds for
supply as per EN 60947-
5-6:
U
= 8.2 V, R
= 1 kΩ
H
i
U
= DC 15.5 V
i
I
= 25 mA
i
P
= 64 mW
i
5.2 nF
Negligible
Floating contact, open
Floating contact, closed
With Ex protection
Ex "ic", "nL", "nA nL", "tD"
6DR4004-6A
-
≥ 2.1 mA
≤ 1.2 mA
Switching thresholds for
supply as per EN 60947-
5-6:
U
= 8.2 V, R
= 1 kΩ
H
i
"ic" / "nL":
U
= DC 25.2 V
i
"nA nL":
U
≤ DC 15.5 V
n
C
= 5.2 nF
i
Negligible
45