Table 3: Model Ratings
Rating
Model
Output Voltage
adjustment
range
Default Output
Voltage
Output Current
Limit
adjustment
range
Default Output
Current Limit
Output V Noise
(mV rms)
Input Current
max at 100Vin
(rms)
Max Output
Voltage for full
current out
LVD
Disconnect
range (Option)
LVD Reconnect
range (Option)
Output Power
Limit
12V
12V 60A 24V 60A 24V 30A 48V 30A 48V 15A
120A
ICT1600 -
ICT800 -
12SC
12SC
11.5V-
11.5V-
15.5V
15.5V
13.8V
13.8V
25 - 120A 13 – 60A
120A
60A
30
30
18A
(<16A @
9A
120V)
13.5V
13.5V
10.0-
10.0-
11.5V
11.5V
11.5-
11.5-
13.0V
13.0V
1600W
800W
ICT1600 -
ICT800 -
24SC
24SC
23.0V –
23.0V –
31.0V
31.0V
27.6V
27.6V
10 - 60A
5 – 30A
60A
30A
30
30
18A
(<16A @
9A
120V)
27V
27V
20.0-23.0V 20.0-23.0V
23.0-26.0V 23.0-26.0V
1600W
800W
ICT1600 -
ICT800 -
48SC
48SC
46.0V –
46.0V –
62.0V
62.0V
55.2V
55.2V
5 - 30A
2.5 – 15A
30A
15A
60
60
18A
(<16A @
9A
120V)
54V
54V
40.0-
40.0-46.0V
46.0V
46.0-
46.0-52.0V
52.0V
1600W
800W