Note that an Equalize Charge can only be initiated when the
battery is fully charged. If the power supply is unable to start
an Equalize charge at the selected Start Time, it will attempt
again at the same time next day.
Equalize Status: This box indicates if the battery is fully
charged and ready for an equalize charge. "Not Ready"
indicates the battery is not fully charged, and an equalize
charge cannot be initiated. When "Ready" the Manual
Equalize button may be clicked to start a single Equalize
cycle.
Last Equalize Charge: Indicates the date and time of the
last Equalize charge.
Charge Time: Indicates the duration of the last Equalize
charge cycle, in minutes.
Next Equalize Charge: The scheduled date and time of the
next Equalize charge, if an Equalize Interval has been set.
Configure Battery: The power supply will use this information to help
determine the battery state of charge, and remaining battery capacity
when in use.
Battery Capacity: Set the Battery Capacity Rating in Ah (50
to 1000 Ah) of the total battery pack connected to the power
system.
Discharge Rate: Set the Battery discharge rate (hrs) used by
the battery manufacturer to determine the battery capacity.
(typically either 10 or 20hrs)
LVD Settings: Set the battery Low Voltage Disconnect and Re-
connect thresholds and LVD alarm functions here, for units with the
optional LVD battery port.
Disconnect Voltage: Set the battery voltage level that will
trigger the opening of the battery Low Voltage Disconnect
relay.
Reconnect Voltage: Set the battery voltage that will trigger
the re-closing of the LVD relay (must be 1.5V > than the
disconnect voltage)