Helios ICT Platinum Series Instruction Manual page 38

Table of Contents

Advertisement

fault. (Note: The form C contact will be activated any time the
unit completely loses AC power, regardless of this setting.)
Send E-mail: If this box is checked, an e-mail alarm
notification will be sent when the AC input is out of range.
OVER-TEMPERATURE ALARM
The alarm latches the output off, and automatically clears when the
internal temperature falls to within a normal operating range.
Activate Alarm Form C Contact: If this box is checked, the
alarm form "C" contacts on the power supply will indicate a
fault condition when an internal or battery over-temperature
limit is exceeded.
Send E-mail: If this box is checked, an e-mail alarm
notification will be sent when an over-temperature failure
occurs.
FAN FAILURE ALARM
This alarm provides a notification when an internal fan failure occurs,
and does not affect the power supply output state.
Activate Alarm Form C Contact: If this box is checked, the
alarm form "C" contacts on the power supply will indicate a
fault condition when a fan failure occurs.
Send E-mail: If this box is checked, an e-mail alarm
notification will be sent when a fan failure occurs.
PARALLEL UNIT OFFLINE ALARM
This alarm does not affect the power supply output state.
Activate Alarm Form C Contact: If this box is checked, the
alarm form "C" contacts on the power supply will indicate a fault
condition if communications is lost between any units
connected together through the serial interface. This setting
has no effect if parallel operation is not active.
Send E-mail: If this box is checked, an e-mail alarm
notification will be sent if communications is lost between any
units connected together through the RS485 interface. This
setting has no effect if parallel operation is not active.
38

Advertisement

Table of Contents
loading

Table of Contents