fault. (Note: The form C contact will be activated any time the
unit completely loses AC power, regardless of this setting.)
Send E-mail: If this box is checked, an e-mail alarm
•
notification will be sent when the AC input is out of range.
OVER-TEMPERATURE ALARM
The alarm latches the output off, and automatically clears when the
internal temperature falls to within a normal operating range.
Activate Alarm Form C Contact: If this box is checked, the
•
alarm form "C" contacts on the power supply will indicate a
fault condition when an internal or battery over-temperature
limit is exceeded.
Send E-mail: If this box is checked, an e-mail alarm
•
notification will be sent when an over-temperature failure
occurs.
FAN FAILURE ALARM
This alarm provides a notification when an internal fan failure occurs,
and does not affect the power supply output state.
Activate Alarm Form C Contact: If this box is checked, the
•
alarm form "C" contacts on the power supply will indicate a
fault condition when a fan failure occurs.
Send E-mail: If this box is checked, an e-mail alarm
•
notification will be sent when a fan failure occurs.
PARALLEL UNIT OFFLINE ALARM
This alarm does not affect the power supply output state.
Activate Alarm Form C Contact: If this box is checked, the
•
alarm form "C" contacts on the power supply will indicate a fault
condition if communications is lost between any units
connected together through the serial interface. This setting
has no effect if parallel operation is not active.
Send E-mail: If this box is checked, an e-mail alarm
•
notification will be sent if communications is lost between any
units connected together through the RS485 interface. This
setting has no effect if parallel operation is not active.
38