USER'S MANUAL
SERVOMOTOR VOLTAGE STABILISER
EMi3
w w w . h e l i o s p s . c o m

Advertisement

Table of Contents
loading

Summary of Contents for Helios Salicru EMi3

  • Page 1 USER'S MANUAL SERVOMOTOR VOLTAGE STABILISER EMi3 w w w . h e l i o s p s . c o m...
  • Page 2 5.2.5. Location. General index 5.3. CONNECTION. 5.3.1. Connection of input terminals. 1. INTRODUCTION. 5.3.2. Connection of output terminals. 1.1. ACKNOWLEDGEMENT LETTER. 5.3.3. Non-critical loads connection. 2. INFORMATION FOR SAFETY. 5.3.4. Connection of the protective earth 2.1. USING THIS MANUAL. 5.3.5. Connection of the communication module.
  • Page 3 8.2. WARRANTY CONDITIONS. 8.2.1. Warranty terms. 8.2.2. Out of scope of supply. 8.3. TECHNICAL SERVICE NETWORK. 9. ANNEXES. 9.1. STANDARD EQUIPMENTS GENERAL TECHNICAL SPECIFICATIONS. USER'S MANUAL EMi3 SERVOMOTOR VOLTAGE STABILISER...
  • Page 4: Acknowledgement Letter

    1. INTRODUCTION. 1.1. ACKNOWLEDGEMENT LETTER. We would like to thank you in advance for the trust you have placed in us by purchasing this product. Read this instruction manual carefully in order to be familiarized with its contents, because, as much as you know and understand the equipment the highest will be your satisfaction and safety levels and their features will be optimized too.
  • Page 5: Information For Safety

    2. INFORMATION FOR SAFETY. 2.1. USING THIS MANUAL. The generic information of the equipment is supplied in digital format in a CD-ROM, and it includes among other documents the own user's manual of the system and the EK266*08 docu- ment concerning to «Safety instructions». Before doing any action over the equipment regarding installation or commis- sioning, change of location, setting or handling, read them carefully.
  • Page 6: Quality And Standard Guarantee

    3. QUALITY AND STANDARD GUARANTEE. 3.3. ENVIRONMENT. This product has been designed to respect the Environment and 3.1. DECLARATION OF THE MANAGEMENT. manufactured in accordance with the ISO 14001 norm. Our target is the client’s satisfaction, therefore this Management Equipment recycling at the end of its useful life: has decided to establish a Quality and Environmental policy, by Our company commits to use the services of authorised socie- means of installation a Quality and Environmental Management...
  • Page 7 4. PRESENTATION. Power Dimen. (mm) Weight Model Voltage (kVA) D. x W. x H. (kg) fig. 4.1. VIEWS. EMi3 M 5-2 EMi3 M 7,5-2 590 x 340 x 585 4.1.1. Equipment views. EMi3 M 10-2 EMi3 M 15-2 Tables from 1 to 8 show the standardised models with their EMi3 M 20-2 physical dimensions and weights, as well as the correlation EMi3 M 25-2...
  • Page 8 Power Dimen. (mm) Weight Power Dimen. (mm) Weight Model Voltage Model Voltage (kVA) D. x W. x H. (kg) fig. (kVA) D. x W. x H. (kg) fig. EMi3 M 5-2 EMi3 M 5-2 590 x 340 x 585 590 x 340 x 585 EMi3 M 7,5-2 EMi3 M 7,5-2 EMi3 M 10-2...
  • Page 9 The dimensions stated in tables 1 to 8 corresponds to standard Power Dimen. (mm) Weight Model Voltage equipments. (kVA) D. x W. x H. (kg) fig. When an equipment includes the manual Bypass option, EMi3 M 5-2 590 x 340 x 585 depending on the model (power and ranges), the physical dimensions can change as regards to the standard model, nev- EMi3 M 7,5-2...
  • Page 10 (CM) (Q1) (Q5) (SL) (PC) (X33) (TB) (PR) (X9) (RV) (X6) (X5) (RD) (X4) (X1) Fig. 1. Views of single phase equipment in case, format nr 1. (CM) (Q1) (RV) (PC) (Q5) (SL) (X33) (TB) (RV) (X9) (X6) (PR) (X5) (RD) (X4) (X1)
  • Page 11 (CT) (PF) (PC) (Q1) (MM) (Q5) (TB) (X33) (SL) (PI) (RV) (X1) (X4) (X5) (X6) (X9) Fig. 4. Views of single phase equipment in cabinet, format nr 1. USER'S MANUAL EMi3 SERVOMOTOR VOLTAGE STABILISER...
  • Page 12 (CT) (PF) (PC) (Q1) (MM) (Q5) (TB) (X33) (SL) (PI) (RV) (X1) (X4) (X5) (X6) (X9) Fig. 5. Views of single phase equipment in cabinet, format nr 2. SALICRU...
  • Page 13 (CT) (PF) (PC) (Q1) (MM) (Q5) (TB) (X33) (SL) (PI) (RV) (X1) (X2) (X3) (X4) (X5) (X6) (X7) (X8) (X9) Fig. 6. Views of three phase equipment in cabinet, format nr 2. USER'S MANUAL EMi3 SERVOMOTOR VOLTAGE STABILISER...
  • Page 14 (PF) (CT) (CT) (PF) (PC) (PI) (RV) (PI) (RV) Fig. 7. Front views of both single and three phase equipments in cabinet, format nr 3. SALICRU...
  • Page 15 (Q1) (Q5) (MM) (TB) (X33) (SL) Fase (X1) Neutro (X4) (X5) Fase (X1) Neutro (X4) (X5) Fig. 8. Front views of single phase equipment in cabinet with door opened, format nr 3. USER'S MANUAL EMi3 SERVOMOTOR VOLTAGE STABILISER...
  • Page 16 (Q1) (Q5) (MM) (TB) (X33) (SL) (X1) (X2) (X3) (X4) (X5) (X6) (X7) (X8) (X9) (X5) Fig. 9. Front views of three phase equipment in cabinet with door opened, format nr 3. SALICRU...
  • Page 17 (CT) (RV) (PF) (t (PC) (PI) (TT) Fig. 10. Front and top view, three phase equipment consisting of three single phase units (to be joined once located). USER'S MANUAL EMi3 SERVOMOTOR VOLTAGE STABILISER...
  • Page 18 Figures 10 and 11 are scaled as regards to the other views of the equipments and their dimensions can be checked in the respective tables 2, 4, 6 and 8 according to the model and voltage range. (Q1) (MM) (Q5) (MM) (TB) (t (X1) (X4) (X5) (X6) (X9) (SL) (X33) (X2) (X4) (X5) (X7) (X9) (SL) (X33) (X3) (X4) (X5) (X8) (X9) (SL) (X33) Fig.
  • Page 19 4.1.2. Legends corresponding to the equipment views. (PC) Control panel with LCD. Connection parts: (PF) Cabinet front door. (X1) Input terminal phase R. (PI) Leveller feet, cabinet base plinth. (X2) Input terminal phase S. ) Rod to joint the equipment through the top and the base (X3) Input terminal phase T.
  • Page 20 4.2. DEFINITION OF THE PRODUCT. 4.2.1. Nomenclature. EMi3 T 20-2TFMR-BM IR WCO ±20% 3x220V T/T ±4% EE595328 Particular client specifications. ±4% Output accuracy, if its different from ±1 %. Input/ouput configuration, star/star. Input/ouput configuration, star/delta. Input/ouput configuration,delta/delta. Input/ouput configuration,delta/star. 3x220V Nominal voltage of equipment.
  • Page 21: Description Of The Equipment

    4.3. PRESENTATION. The LCD of the control panel of the stabilizer allows checking the input/output voltages and frequency, whenever you need. EMi3 stabilizer model has been designed to operate in fluc- Also, the LCD has measurements of output current, active and tuated mains and to safeguard the critical loads, in particular, apparent powers per phase and total, power factor per phase those ones with a complicated nature: high inrush start up cur-...
  • Page 22: Operating Principle

    As standard, input voltage range of ±15 %, being able to • The LCD panel shows the values of the input/output voltages manufacture ranges up to ±30 %. and frequency. The measurement of output current, active and apparent powers, power factor are available with the output High efficiency, up to 97,5 %.
  • Page 23 Automatic. • As an option, if the application would need it, the range could be The system will supply output voltage meanwhile the extended from the standard ±15 % to a wide one (i.e. ±25 %), by requesting an equipment with extended voltage range. voltage is inside the preset range, otherwise the output will be broken.
  • Page 24 Configuration adaptor: delta-star or vice versa...). • 4.7.6. Communication and dry contacts module. And even combining the two above options depending on • The communication module has several communication ways the case. with the external environment. In general, it can be said, that beside of the Slot to insert the SICRES Ethernet communication As a result of the possible combinations, this document does card, there are several communication ports and 9 dry contacts...
  • Page 25 Output circuit breakers or Input circuit breaker swicthes Manual bypass switch or breaker • • • EMi3 power supply Load power supply Fig. 14. Manual bypass panel single line diagram including input and output switches. USER'S MANUAL EMi3 SERVOMOTOR VOLTAGE STABILISER...
  • Page 26: Installation

    In case peripheral elements are added at the input or output • 5. INSTALLATION. like transformers or autotransformers, The current of the nameplates of these elements has to be considered in order Read and respect the Safety Information, described • to select the suitable cross cable section, by respecting the in section 2 of this document.
  • Page 27: Equipment Reception

    must be removed, by taking the needed cautions as regards To move it, use a pallet jack or forklift through the own base to the local and/or national regulations. of the cabinet. Proceed to unpack the equipment. To do that, cut the strips •...
  • Page 28 Or come with one separate earth cable to each terminal In case were needed to change the location of the equip- ˆ • (screw) (X5) of each equipment, but they have to come ments, these joint rods have to be removed previously. from the same point.
  • Page 29 unit with star configuration, because if the line is con- Or come with one separate earth cable to each terminal ˆ nected instead of the neutral, the load will suffer a high (screw) (X5) of each equipment, but they have to come over voltage that can destroy it.
  • Page 30 ling of all of them. Manual Bypass panel In case of discrepancies between the labelling and the instruc- • tions of this manual, the labelling will always prevail. EMi3 Stabilizer Line To loads Fig. 15. Connection of the stabilizer with a manual Bypass Panel with single cam switch.
  • Page 31 6. OPERATING. 6.2.1.1. Procedure Turn the input switch of the switchgear panel «On». • 6.1. CONTROLS BEFORE COMMISSIONING. Turn the input switch (Q1) «On» of the stabiliser. The fo- • llowing message will be displayed: Make sure that all the connections have been made prop- •...
  • Page 32 It is always recommended to wait 10 s, when the input circuit 6.4. MANUAL BYPASS PANEL, OPTION. breaker or switch (Q1) is turned to position «I» or «On», in order to give time to a supposed extreme correction of the input voltage. In the start up and shutdown procedure of the stabilizer are •...
  • Page 33: Control Panel

    7. CONTROL PANEL. 7.2. BASIC FUNCTIONS OF THE KEYS AND NOTES. LCD panel. (b) (a) «ENT» key. «ESC» key. Upward key « ». Backward key « ». Right key« ». Left key « ». By means of the upward « »...
  • Page 34 EMi3 x x x x.x KVA SERIAL NUMBER FIRM VERSION   x x x.x V  x x x x x x x x x x  ODY: x x APP: x x    Screen 0.1 Screen 0.2 Screen 0.3 ...
  • Page 35 EMi3 x x x x.x KVA SERIAL NUMBER FIRM VERSION   x x x.x V x x x x x x x x x x ODY: x x APP: x x      Screen 0.1 Screen 0.2 Screen 0.3 ...
  • Page 36 Screen 2.4 Enabling Screen alarm Description level With Manual selection, the screen 2.3, supplies voltage to the ALARM INPUT Input voltage higher than the In single phase VOLTAGE HIGH nominal + the high range. equipment. motor in clock or counter clock wise in order to increase or de- crease the voltage by means of «...
  • Page 37 The voltage values that the end-user will be able to select in Enabling Screen alarm Description level the setting menu for a single or three phase structure and high or low voltage will depend in the constructive features of the ALARM FAIL Parameter system not coherent.
  • Page 38: Maintenance, Warranty And Service

    If the EMi3 has a serious overload, the coal of the brush • 8. MAINTENANCE, WARRANTY AND SERVICE. can be damaged, even if there is not any visible damage in the winding. 8.1. BASIC TROUBLESHOOTING GUIDE FOR PREVENTIVE Contact with our Service and Technical Support MAINTENANCE.
  • Page 39 9. ANNEXES. 9.1. STANDARD EQUIPMENTS GENERAL TECHNICAL SPECIFICATIONS. Input Single phase 220 / 230 or 240 V (phase + neutral and PE) Voltage Three phase 3x380 / 3x400 / 3x415 V (3 phases + neutral and PE) Other voltages and configurations under request Range ±...