Configure the Battery Equalize Charge voltage, duration, and
automatic repeat interval if desired when using flooded lead-
acid type batteries only. The system will step up the output
voltage to the Equalize Voltage for the Equalize Duration time
whenever the Equalize Status is set to Enable (or automatically
each interval time when an Interval is set) once the battery is
fully charged.
WARNING!
Potential for personal injury, or damage to property and
equipment due to overcharging of the external battery!
Use Equalize charge on flooded lead-acid batteries only. Refer
to Battery manufacturer's instruction manual. Do not use this
feature on any type of sealed battery.
Ensure the battery compartment is well ventilated to avoid any
risk of explosion!
Do not exceed the Equalize voltage setting recommended by the
battery manufacturer.
Always consult with battery manufacturer and observe all
battery manufacturer recommendations.
Voltage: Set the Equalize voltage level recommended by the
battery manufacture. (Use with flooded lead-acid batteries only!
Always consult with battery manufacturer and observe all
battery manufacturer recommendations.)
Duration: Set the maximum time (in minutes) for the equalize
charge to be applied, as recommended by the battery
manufacturer.
Status: Set to Start, to begin an equalize charge when the
battery is fully charged. (Status will be READY if battery is fully
charged. Status will show IN PROGRESS when the equalize
charge is occurring)
17