Electrical installation
4.5 Connections
1. Feed the cable for the Control Unit into the cabinet from the bottom left.
2. Remove approx. 3 cm of the cable insulation at the level of the shield plate in the lower
part of the cabinet and attach the cable there.
3. To secure the cable in accordance with EMC requirements, snap the clip onto the shield
plate.
4. Use cable ties to secure the cable at suitable points.
5. Route the cable further in the cabinet to the upper side of the Control Unit. When doing
so, route the cable in a similar manner to the standard cables that have already been
installed in the cabinet.
6. Use cable ties to secure the cable at suitable points.
7. Connect the cable to the Control Unit.
(→See SINAMICS S120 Manual GH1 Control Units)
98
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A