6.4.2.3

X1 - power supply

-X1: Power supply
Table 6- 31
L1
L2
L3
PE
Max. connection cross-section: 4 mm², recommended cross-section: 2.5 mm²
6.4.2.4
X6 - external 24 V DC power supply
When required, the 24 V DC power supply can be connected externally via terminal strip X6.
To do this, open the jumpers at terminals X6:6,7 and X6:8,9.

X6: External 24 V DC power supply

Table 6- 32
7
9
PE
Max. connection cross-section: 4 mm², recommended cross-section: 2.5 mm²
The maximum cable length that can be connected is 10 m.
NOTICE
Inadmissible equalization currents as a result of potential differences when using different
power supply sources
Using different power sources for the Heat Exchanger Module and the other Cabinet
Modules can result in potential differences and inadmissible equalizing currents flowing
through the DRIVE-CLiQ interface of the TM31 Terminal Module.
• For the external 24 V DC power supply of the control box, use the same power supply
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Terminal strip X1
Terminal
Function
Phase L1
Phase L2
Phase L3
PE connection
Terminal strip X6
Terminal
Function
+
M
PE connection
that is used for the other Cabinet Modules in the same DRIVE-CLiQ line.
Technical data
Voltage:
3 AC 380 V -10 % ... 3 AC 415 V +10 %
or
3 AC 660 V -10 % ... 3 AC 690 V +10 %
Current consumption: See Technical data
Technical data
Voltage: 24 V DC (20.4 to 28.8 V)
Current consumption: max. 1.0 A