X41 Ep Terminal / Temperature Sensor Connection - Siemens SINAMICS S120 Manual

Cabinet modules liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

6.3.2.3

X41 EP terminal / temperature sensor connection

Table 6- 23
Terminal strip X41 EP terminals / temperature sensor connection
Terminal
1
2
3
4
Max. connectable cross-section: 2.5 mm
Danger to life due to electric shock in the event of voltage flashovers at the temperature
sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Only use temperature sensors that fully comply with the specifications of the safety
• If safe electrical separation cannot be guaranteed (for linear motors or third-party
NOTICE
Device failure as a result of unshielded or incorrectly routed cables to temperature sensors
Unshielded or incorrectly routed cables to temperature sensors can result in interference
being coupled into the signal processing electronics from the power side. This can result in
significant disturbance of all signals (fault messages) up to failure of individual components
(destruction of the devices).
• Only use shielded cables as temperature sensor cables.
• If temperature sensor cables are routed together with the motor cable, use separately
• Connect the cable shield to ground potential through a large surface area.
• Recommendation: Use suitable Motion Connect cables.
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Function
EP M1
(Enable Pulses)
EP +24 V
(Enable Pulses)
- Temp
+ Temp
2
WARNING
isolation.
motors, for example), use a Sensor Module External (SME120 or SME125) or Terminal
Module TM120.
shielded cables twisted in pairs.
Technical data
Supply voltage: 24 VDC (20.4 to 28.8 V)
Current consumption: 10 mA
Signal propagation times:
L → H: 100 μs;
H → L: 1000 μs
The pulse inhibit function is only available when Safety Integrated Basic
Functions are enabled.
Temperature sensor connection for motor temperature measurement:
KTY84-1C130, PTC, PT100, bimetallic switch with NC contact
Cabinet Modules
6.3 Motor Modules
175

Advertisement

Table of Contents
loading

Table of Contents