Minimum cable lengths for parallel connection and connection to a motor with a single-winding
system
Note
Minimum cable lengths
The minimum cable lengths specified in the table below must be observed when two or more
Motor Modules are connected in parallel and there is a connection to a motor with a single-
winding system. The motor cables of Motor Modules connected in parallel may only be
connected with one another at the motor terminal box.
A motor reactor (option L08) must be used if the required cable length cannot be reached in
the application.
Table 6- 21
Motor Modules, 510 ... 720 VDC
Article No.
6SL3725-1TE36-1AA3
6SL3725-1TE37-5AA3
6SL3725-1TE38-4AA3
6SL3725-1TE41-0AA3
6SL3725-1TE41-2AA3
6SL3725-1TE41-4AA3
6SL3725-1TE41-4AS3
Table 6- 22
Motor Modules, 675 ...1035 VDC
Article No.
6SL3725-1TG34-7AA3
6SL3725-1TG35-8AA3
6SL3725-1TG37-4AA3
6SL3725-1TG38-0AA3
6SL3725-1TG38-1AA3
6SL3725-1TG41-0AA3
6SL3725-1TG41-3AA3
6SL3725-1TG41-6AA3
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Frame size
P
[kW]
rated
HXL
315
HXL
400
HXL
450
JXL
560
JXL
710
JXL
800
JXL
800
Frame size
P
[kW]
rated
HXL
450
HXL
560
HXL
710
HXL
800
JXL
800
JXL
1000
JXL
1200
JXL
1500
6.3 Motor Modules
I
[A]
Minimum length [m]
rated rms
605
13
745
10
840
9
985
8
1260
6
1405
5
1330
5
I
[A]
Minimum length [m]
rated rms
465
25
575
20
735
18
810
18
810
15
1025
10
1270
8
1560
7
Cabinet Modules
173