Infeed terminal in the Basic Line Connection Module or Active Line Connection Module
The terminal in the Basic Line Connection Module or the Active Line Connection Module
comprises the X100 terminal block for feeding in the auxiliary voltages. No voltage taps are
available to the customer. When option K76 is available (auxiliary power generation in the
Line Connection Module), then terminal X100 is already assigned in the factory.
Table 4- 6
X100, terminal block in the Basic Line Connection Module or Active Line Connection Module to feed in the
auxiliary voltages
Terminal
Voltage tap
1
230 V 1 AC (max. 265 VAC)
1
2
2
3
24 VDC for the electronics power supply (max. 30 VDC)
3
4
4
The maximum current rating of the auxiliary power supply system is 28 A.
Max. connectable cross-section: 10 mm
Note
External infeed
An external customer infeed to the auxiliary power supply system can be connected at
terminal block X100 of the Basic Line Connection Module or the Active Line Connection
Module.
Connecting cables
Table 4- 7
Phase
1 ≙ L1
3 ≙ N
1 ≙ P24
4 ≙ M
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
2
Voltage assignment for connecting cables
Assigned voltages
1 AC 230 V (max. AC 265 V)
The cable labeled "1" must be connected to terminal X140:1, the cable labeled "3"
must be connected to terminal X140:3.
24 V DC for the electronics power supply (max. 30 V DC)
The cable labeled "1" must be connected to terminal X150:1, the cable labeled "4"
must be connected to terminal X150:4.
Electrical installation
4.5 Connections
Rated current
Max. 28 A
Max. 28 A