9.15 K52, Additional SMC30 Sensor Module

Removing the connector jumper in the Voltage Sensing Module VSM10
At the Voltage Sensing Module (VSM10), the connector jumper in terminal X530 on the
lower side of the component must be removed if you are using the cabinet unit on a non-
grounded line supply (IT system).
Use two screwdrivers or a suitable tool in order to relieve the holding springs in the terminal
and then withdraw the connector jumper.
Terminal X530 with connector jumper
9.15
K52, Additional SMC30 Sensor Module
Availability of option
This option is available for the following S120 Cabinet Modules:
● Motor Modules
Description
With option K50, an SMC30 Sensor Module is included in the cabinet unit. The additional
SMC30 Sensor Module enables reliable actual value acquisition when using Safety
Integrated Extended Functions.
Note
Safety Integrated Function Manual
Detailed and comprehensive instructions and information for the Safety Integrated functions
can be found in the associated Function Manual. This manual is available as additional
documentation on the customer DVD supplied with the device.
338
Relieve the springs and withdraw the connector
jumper
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A