NOTICE
Damage to the encoder due to incorrect supply voltage
The encoder power supply can be parameterized to 5 V or 24 V. The encoder may be
damaged if you enter the wrong parameter.
• Select the appropriate supply voltage.
Note
Cable shield for the encoder connection via terminals
Note that when the encoder is connected via terminals, the cable shield must be applied to
the module.
9.13.4

Connection example

Connection example 1: HTL encoder, bipolar, without zero mark -> p0405 = 9 (hex)
Figure 9-26
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Connection example 1: HTL encoder, bipolar, without zero mark
9.13 K50, Sensor Module Cabinet-Mounted SMC30
Options
335