Options
9.13 K50, Sensor Module Cabinet-Mounted SMC30
X521/X531 encoder connection 2 for HTL/TTL/SSI encoder with open-circuit monitoring
Table 9- 25
Encoder connection X521
Terminal
1
2
3
4
5
6
7
8
Max. connectable cross-section: 1.5 mm²
Note
Operation of unipolar HTL encoders
When unipolar HTL encoders are used, terminal block A*, B*, and R* must be jumpered with
M encoder (-X531).
Table 9- 26
Encoder connection X531
Terminal
1
2
3
4
5
6
7
8
Max. connectable cross-section: 1.5 mm²
NOTICE
Damage to the motor in the event of incorrectly connected KTY temperature sensor
A KTY temperature sensor connected with incorrect polarity cannot detect if the motor
overheats. Overheating can cause damage to the motor.
• Connect a KTY temperature sensor with the correct polarity.
334
Signal name
A
A*
B
B*
R
R*
CTRL
M
Signal name
P encoder 5 V / 24 V
M encoder
- Temp
+ Temp
Clock
Clock*
Data
Data*
Technical data
Incremental signal A
Inverted incremental signal A
Incremental signal B
Inverted incremental signal B
Reference signal R
Inverted reference signal R
Control signal
Ground
Technical data
Encoder power supply
Ground for encoder power supply
Motor temperature sensing KTY84-1C130 (KTY-) Tem-
perature sensor KTY84-1C130/PTC/
bimetallic switch with NC contact
SSI clock
Inverted SSI clock
SSI data
Inverted SSI data
Cabinet Modules liquid cooled