Table 9- 46
Table 9- 47
Commissioning
When commissioning, the dV/dt filter must be registered with STARTER or using the AOP30
operator panel (p0230 = 2).
Note
Reset when establishing the factory setting
Parameter p0230 is reset when the factory setting is established. The parameter has to be
reset when recommissioning.
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Maximum permissible motor cable lengths for the DC-link voltage 510 - 720 VDC
Frame sizes FXL, GXL, HXL
Shielded cable max. 300 m or
unshielded cable max. 450 m
6SL3725-1TE36-1AA3
6SL3725-1TE37-5AA3
6SL3725-1TE38-4AA3
-
Maximum permissible motor cable lengths for the DC-link voltage 675 - 1035 VDC
Frame sizes FXL, GXL, HXL
Shielded cable max. 300 m or
unshielded cable max. 450 m
6SL3725-1TG34-7AA3
6SL3725-1TG35-8AA3
6SL3725-1TG37-4AA3
6SL3725-1TG38-0AA3
9.25 L10, dV/dt filter plus Voltage Peak Limiter
Frame size JXL
Shielded cable max. 150 m or
unshielded cable max. 225 m
6SL3725-1TE41-0AA3
6SL3725-1TE41-2AA3
6SL3725-1TE41-4AA3
6SL3725-1TE41-4AS3
Frame size JXL
Shielded cable max. 150 m or
unshielded cable max. 225 m
6SL3725-1TG38-1AA3
6SL3725-1TG41-0AA3
6SL3725-1TG41-3AA3
6SL3725-1TG41-6AA3
Options
379