Cabinet Modules
6.2 Active Line Connection Modules
Table 6- 20
Technical data for Active Line Connection Modules, 3 AC 500 ... 690 V
Article No.
Rated power
- for I
(50 Hz 690 V)
N DC
- for I
(50 Hz 690 V)
H DC
- for I
(50 Hz 500 V)
N DC
- for I
(50 Hz 500 V)
H DC
- for I
(60 Hz 575 V)
N DC
- for I
(60 Hz 575 V)
H DC
DC-link current
- Rated current I
N DC
- Base load current I
1)
H DC
- Maximum current I
max DC
Input/regenerative feedback current
- rated current I
N E
- maximum current I
max E
Supply voltages
- Line voltage
- Line frequency
- Electronics power supply
- DC-link voltage
Current drain (1 AC 230 V)
Current consumption of the electronics (24 V DC) A
DC-link capacitance
- Active Line Module
- Drive line-up, max.
Power loss, max., at 50 Hz 690 V
- <IP55:
- dissipated to the coolant
- dissipated to the ambient air
- IP55:
- dissipated to the coolant
- dissipated to the ambient air
Material of the integrated heat exchanger
- Active Line Module
- Active Interface Module
Rated flow rate
- degree of protection <IP55
- degree of protection IP55
Pressure drop, typical
at the rated flow rate
3)
Volume of liquid
- degree of protection <IP55
- degree of protection IP55
Cooling air requirement
Sound pressure level L
pA
Line connection L1, L2, L3
- connection cross-section, max (IEC)
164
2)
(1 m) at 50/60 Hz
4)
6SL3735-
7TG41-0LA3 7TG41-3LA3 7TG41-6LA3
kW
1100
kW
1000
kW
780
kW
710
hp
1250
hp
1000
A
1147
A
1022
A
1722
A
1025
A
1537
V
3 AC 500 -10 % ... 3 AC 690 +10 % (-15 % < 1 min)
ACrms
Hz
V
DC
V
DC
A
1.2
1.77
µF
19330
µF
153600
kW
21.5
kW
3.1
kW
23.7
kW
0.9
Aluminum
Aluminum
l/min
43
l/min
43.7
Pa
150000
dm³
14
dm³
17.6
m
/s
0.272
3
dB(A)
71/71
5/M12 +
mm
4/M16
2
8 x 240
1400
1700
1215
1490
965
1180
880
1080
1500
1855
1250
1530
1422
1740
1266
1550
2133
2620
1270
1560
1905
2055
47 ... 63 Hz
24 (20.4 ... 28.8)
1.5 x U
line
1.2
1.2
1.63
1.67
19330
21000
153600
210000
27.3
36.7
3.7
4.4
30.1
40.2
0.9
0.9
Aluminum
Aluminum
Aluminum
Aluminum
43
43
43.7
43.7
150000
150000
14
14
17.6
17.6
0.272
0.272
71/71
71/71
5/M12 +
5/M12 +
4/M16
4/M16
8 x 240
8 x 240
Cabinet Modules liquid cooled