Connections; Cable Lugs - Siemens SINAMICS S120 Manual

Cabinet modules liquid-cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.5

Connections

4.5.1

Cable lugs

Cable lugs
The cable connections on the devices are designed for cable lugs according to DIN 46234 or
DIN 46235.
For connection of alternative cable lugs, the maximum dimensions are listed in the table
below.
These cable lugs are not to exceed these dimensions, as mechanical fastening and
adherence to the voltage distances is not guaranteed otherwise.
Figure 4-2
Table 4- 2
Dimensions of the cable lugs
Screw / bolts
Connection cross-section
M8
M10
M10
M12
M12
M12
M16
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Dimensions of the cable lugs
d2
[mm²]
[mm]
70
8.4
185
10.5
240
13
95
13
185
13
240
13
240
17
b
l
[mm]
[mm]
24
55
37
82
42
92
28
65
37
82
42
92
42
92
Electrical installation
4.5 Connections
c1
c2
[mm]
[mm]
13
10
15
12
16
13
16
13
16
13
16
13
19
16
73