Figure 7-10 Removing a T/H sensor (NetCol5000-C030/C032)
Step 5 Install the new T/H sensor at the original position, and connect the cable
terminals to the T/H sensor.
Step 6 Install the air filter. Close and lock the rear door, tap Start on the home screen of
the display module.
----End

7.4.7 Replacing a Supply Air Temperature Sensor

Prerequisites
Context
Temperature sensors can be replaced with power-on.
Recommended tools: diagonal pliers, cable tie, Phillips screwdriver
Preparation: Maintain from the front door.
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
Issue 06 (2022-12-15)
NO TE
Before installing the new T/H sensor, ensure that its DIP switch setting is consistent with
that on the original T/H sensor. That is, the first toggle switch is ON, and the others are
OFF.
A supply air temperature sensor needs to be replaced.
A spare temperature sensor of the same model is available and functional.