6. Application information

The interface module can be configured in any slot of the CS7 subrack. A maximum of three interface modules
can be configured for each CS7. No specific sequence has to be followed.
The board must be screwed to the guide rails for perfect functioning, even during start-up.
If the board is inserted in an adapter, the front panel must be connected to the rack housing through a short
cable.
The board may neither be inserted nor withdrawn under voltage.

7. Shielding

The bus cable shield must be grounded, through the largest possible surface area, where the cable enters the
cabinet. The cable shield must be connected to the grounding rail where the cable enters the cabinet. Further,
the shield in the connector housing must be connected to the housing. The connector must be screwed to the
module.
The SIMADYN D EMC Directives and Installation Guidelines /2/ are valid.

8. Additional components

Designation:
CS7 subrack
Following data and additional bus components (e.g. fiber-optic
cables) refer to Catalogs IK10 and ST76 (1996)
SINEC L2 bus cable (e.g.:)
SINEC L2 DP connector
12 Mbaud (e.g.:)
Siemens AG Dk-No. 247463
SIMADYN D Hardware User Manual