5.5.2

EL6652-0000 - Configuration parameters

Index 0xF800 Scanner Settings
Index
F800:0
F800:1
F800:3
F800:4
F800:5
F800:6
F800:7
F800:8
F800:20
F800:21
F800:22
F800:23
F800:24
F800:25
F800:26
F800:27
F800:28
F800:29
F800:2A
F800:2B
Index 0xF900 Scanner Info
The current valid settings are displayed here; these can differ from the object 0xF800. The object 0xF900
displays the active parameters to you.
EL6652-00x0
Name
Master settings
Number
Product Name
Device Type
Vendor ID
Product Code
Revision
Serial Number
MAC address
IP address
Network Mask
Gateway Adress
DHCP Max Retries
TCP/IP TTL
TCP/IP UDP Checksum
TCP/IP TCP Timeout
MultiCast TTL
MultiCast UDP Checksum RW
Forward Class3 to PLC
Advanced Slave Options
Version: 2.5
Access
Meaning
RO
Box Id
RW
Name of the device
RO
Device type
RO
Vendor number
RO
Product code
RO
Version
RO
Serial number (see object 0xF900)
RO
MAC address (see object 0xF900)
RW
= 0 means DHCP enabled, any other
value results in fixed IP Address
RW
= 0 means DHCP enabled, any other
value results in fixed SubNetMask
RW
= 0 means DHCP enabled, any other
value results in fixed Gateway
Address
RW
0-infinite (number of dhcp retries
(actually only infinite retries
implemented)
RW
Time to live for Unicast TCP/UDP
Communication
RW
0-UDP Checksum disabled, 1-UDP
Checksum enabled
RW
Tcp Idle Timout in seconds (0-Timout
disabled)
RW
Time to live for Multicast UDP
Communication
0-UDP Checksum disabled, 1-UDP
Checksum enabled
RW
Forward Explicit Messaging to PLC
(actually not implemented)
RW
Store Category (Bit9=Cat2,
Bit8=Cat1) see Writing the IP address
from the PLC [} 94]