Safety Parameters - Beckhoff EL1904 Operating Instructions Manual

Twinsafe terminal with 4 digital fail-safe inputs
Hide thumbs Also See for EL1904:
Table of Contents

Advertisement

Product designation
Permitted operating environment
Correct installation position
Approvals
Derating table for altitudes above 2000 m
The derating table (table 8) from the IEC 61131-2:2017 standard can be referred to for the use of the
TwinSAFE components above the specified maximum altitude.
Altitude in m
2
0 to 2000
3000
4000
5000
Note: Linear interpolation is permissible between the altitudes
1)
Ambient temperature of the device at an altitude of 2000 m
2)
The air pressure and air density increase as the altitude decreases. Therefore the derating factor for 0 to
2000 m (1.0) is used for altitudes below sea level.
Calculation example
In the following example the calculation is performed for a TwinSAFE component at an operating altitude of
4000 m.
Permissible ambient temperature up to 2000 m above sea level = 55 °C
Permissible ambient temperature up to 4000 m above sea level = 55 °C * 0.8 = 44 °C
Compliance with the temperature limits
The TwinSAFE component has a maximum internal temperature at which a switch-off takes place. This is
designed for the maximum permissible ambient temperature. If the derating factor for the temperature for
higher altitudes is used, the user is solely responsible for ensuring that the calculated maximum ambient
temperature is complied with.
4.4

Safety parameters

Characteristic numbers
Lifetime [a]
Prooftest Interval [a]
PFH
D
%SIL3
PFD
%SIL3
MTTF
d
DC
Performance level
Category
HFT
2
Element classification
1. Special proof tests are not required during the entire service life of the EL1904 EtherCAT terminal.
2. Classification according to IEC 61508-2:2010 (chapter 7.4.4.1.2 and 7.4.4.1.3)
EL1904
EL1904
In the control cabinet or terminal box, with minimum protection
class IP54 according to IEC 60529
see chapter Installation position and minimum distances [} 27]
CE, cULus, ATEX, TÜV SÜD
Derating factor for the temperature
1.0
0.9
0.8
0.7
CAUTION
EL1904
20
1
not required
1.11E-09
1.11%
8.29E-05
8.29 %
high
high
PL e
4
1
Type B
Version: 3.0.0
Product description
1
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents