4.4

Safety parameters

Key data
Lifetime [a]
Prooftest Interval [a]
PFH
D
PFD
MTTF
D
DC
Performance level
Category
HFT
2
Classification element
1. Special proof tests are not required during the entire service life of the EtherCAT Terminal.
2. Classification according to IEC 61508-2:2010 (chapter 7.4.4.1.2 and 7.4.4.1.3)
The EtherCAT Terminals can be used for safety-related applications within the meaning of IEC 61508:2010
up to SIL3 and EN ISO 13849-1:2015 up to PL e (Cat4).
Further information on calculating or estimating the MTTF
TwinSAFE Application Guide or in EN ISO 13849-1:2015 , Table K.1.
In terms of safety-related parameters, the Safety-over-EtherCAT communication is already considered with
1% of SIL3 according to the protocol specification.
4.5

Safe input

The safe inputs and associated clock outputs are implemented as a single channel for each module. This
has the advantage that any channels, e.g. for a two-channel safe sensor, can be combined and used. For
error evaluation of these two channels, the Module Fault Link active parameter of the two modules involved
must be set to TRUE. This is the default state of this parameter.
Clocked signals inside a sheathed cable
If clocked signals (clock outputs for the safe inputs) of different modules are used within a sheathed cable,
a fault of one module, such as cross-circuit or external feed, must lead to the disconnection of all of these
modules. This is achieved by setting the Module Fault Link active parameter for all modules involved. This
parameter is set to TRUE by default.
Safe inputs in Kat.4 / PL e
If two safe input channels are to be used in a Category 4 structure, please ensure that you always combine
an even and an odd channel number.
EL1918 and EL1918-2200
EL1918 and EL1918-2200
20
1
not required
3.00 E-09
4.90 E-05
High
High
PL e
4
1
Type B
value from the PFH
D
DANGER
DANGER
Version: 2.0.0
Product description
value can be found in the
D
25