1.
Mounting Procedure
Mounting Procedure
1. Cut out the mounting panel (max. thick: 5 mm) to match the dimensions shown below.
Panel cut-out hole
2. Insert four fixtures attached to the Simple POD into the mounting holes, and tighten them with the
locking screws.
<Tightening torque: 0.3 to 0.5 N•m>
Mounting hole
3. Mount the gasket so that it will be sandwiched securely between the unit and the mounting panel.
Mounting Angle
Install the unit within the angle of 0° to 135° as shown on the right.
Mounting panel
Fixtures
Mounting panel
Mounting hole
Simple POD unit
1. Mounting Procedure
• Panel cut-out dimensions
(Unit: mm)
+0.5
174
-0
Fixture dimensions
(Unit: mm)
17.8
90°
135°
3-1
3
10.5
Display
0°