5.

Modular Jack (MJ1)

This is a modular connector used for connection for screen data transfer, temperature controller,
barcode reader, card recorder (UG00P-MR) or serial extension I/O (UG00P-U2).
Pins of modular jack 1 correspond to signals as given below.

Editor Setting

1. The use of modular jack 1 can be set on the editor.
2. Select [Modular] from the [System Setting] menu. The [Modular Jack] dialog is displayed. Select
the use of modular jack 1 from the following options.
*1
Refer to the next section "Transferring Screen Data".
*2
Select this option when connecting the card recorder (UG00P-MR).
*3
Refer to the next section "Barcode Reader Connection".
*4
Select this option when connecting the serial extension I/O (UG00P-U2).
*5
Select this option when "Multi-link 2" is selected for [Connection] and "1" is set for [Local Port] on the
[Comm. Parameter] dialog.
*6
Select this option when connecting the temperature controller network or PLC2Way.
*7
Select this option for UG-Link connection.
*8
Select this option when using the ladder transfer function.
*9
Select this option for Modbus slave connection.
*10 Select this option when connecting the printer with serial interface.
Refer to page 2-11.
Side View
MJ1/2
Pin No.
1 2 3 4 5 6 7 8
Modular Jack 1
*1
[Editor Port]
[Card Recorder]
*3
[Barcode]
*4
[UG00P-U2]
*5
[Multi-Link]
[Temp./PLC2Way]
*7
[UG-Link]
*8
[Ladder Tool]
[Modbus Slave]
[Printer (Serial Port)]
5. Modular Jack (MJ1)
Signal Name
1
+SD/RD
−SD/RD
2
3
+5 V
4
+5 V
5
SG
6
SG
7
RD
8
SD
*2
*6
*9
*10
2-9
Contents
RS-485 + data
RS-485 − data
Externally supplied +5 V
MAX 150 mA
Signal ground
RS-232C receive data
RS-232C send data