Connection Examples For Digital Power Outputs; Figure 28: H-Side/L-Side 2; Figure 29: H-Side/H-Side 2; Table 24: Output Configurations And Response Thresholds Of The External Voltage Monitoring - WAGO 750-666/000-003 Manual

Wago-i/o-system 750 4fdi/2fdo 24v/10a profisafe v2 ipar, 4-channel digital input and 2-channel digital output module profisafe v2 ipar, 24v/10a semiconductor power output
Hide thumbs Also See for 750-666/000-003:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
6.3.3

Connection Examples for Digital Power Outputs

The PROFIsafe I/O module includes two semiconductor switches O1 and O2 that
can be used in four different output configurations to switch from loads up to 10
A rated current.
Digital power output O1 always switches in H-Side mode (High Side) to 24V
potential.
Digital power output O2 can either switch in H-Side mode (High Side) to 24V
potential or in L-Side mode (Low Side) to 0V potential depending on the output
configuration.

Table 24: Output configurations and response thresholds of the external voltage monitoring

H-Side/L-Side 1
Figure 26: H-Side/L-
Side 1
U
O1Bmin.
U
O1Bmax.
U
O2Amin.
U
O2Amax.
The Output Configuration parameter is used to configured the connection type
used (see Output Configuration parameters).
Manual
Version 1.2.0, valid from HW/SW Version 01/01
H-Side/H-Side 1
Figure 27: H-Side/H-
Side 1
Response thresholds of the external voltage monitoring
3.9V
U
O2Bmin.
10.98V
U
O2Bmax.
1.28V
-
1.64V
-
H-Side/L-Side 2
Figure 28: H-Side/L-
Side 2
1.39V
U
O1Bmin.
3.92V
U
10.98V
O1Bmax.
-
U
O2Amin.
-
U
O2Amax.
Connect Devices
H-Side/H-Side 2
Figure 29: H-Side/H-
Side 2
3.9V
U
O1Bmin.
U
10.98V
O1Bmax.
1.28V
U
O2Bmin.
1.64V
U
O2Bmax.
65
3.9V
1.39V
3.92V

Advertisement

Table of Contents
loading

Table of Contents