28
Device Description

Table 10: Display elements, communication / I/O module status

Figure 10: Display
elements,
communication / I/O
module status
The group error LED (LED E) can illuminate alone or in conjunction with other
LEDs. Detailed information about the occurred group error is available in the
section "Diagnostics".
Behavior when group error LED (LED E) is flashing
A flashing group error LED (LED E) indicates that the PROFIsafe I/O module
has detected an internal safety critical error. The cause can be a defect in the
PROFIsafe I/O module or an environmental EMC error. In this case, switch off
the PROFIsafe I/O module completely and the switch it back on.
If the problem occurs several times, it points to a defect in the PROFIsafe I/O
module. In this case, return the PROFIsafe I/O module to WAGO Kontakttechnik
GmbH & Co. KG for fault analysis.
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
LED
Designation
E
Group error
Internal bus
F
communication
PROFIsafe
G
status
H
Parameter Setting
Version 1.2.0, valid from HW/SW Version 01/01
WAGO-I/O-SYSTEM 750
Status
Function
Off
No error
Group error, illuminates when
• Overtemperature
• Overvoltage of the
field supply voltage
• Undervoltage of the
Red
field supply voltage
• Error on clock output T1 or T2
• Internal error
• I/O error
• Incorrect F parameters
• Invalid iParameters
Red 2 Hz
Internal safety critical error
flashing
Green
Internal bus communication active
Red
Internal bus communication error
Off
PROFIsafe data exchange not active
Green
PROFIsafe data exchange active
Green
Acknowledgement by operator
0.5 Hz
required
flashing
(Operator acknowledge, OA)
No valid PROFIsafe F parameters
Red
available
Red 1 Hz
Watchdog time (F_WD_Time)
flashing
exceeded
Off
Parameterization OK
PROFIsafe I/O module selected by
Red
WAGO-I/O-CHECK
Red 1 Hz
iParameter invalid
flashing
Red 2 Hz
Configuration running and not yet
flashing
completed
Green 2
PROFIsafe I/O module is it PROFIsafe
Hz
test mode
flashing
Manual