INIM SmartLoop Series Installation Manual

INIM SmartLoop Series Installation Manual

Analogue fire alarm control panel
Hide thumbs Also See for SmartLoop Series:
Table of Contents

Advertisement

SmartLoop
Analogue fire alarm control panel
Installation manual
EN 54-2
EN 54-4
0051-CPD-0225
0051-CPD-0226
0051-CPD-0227
0051-CPD-0228
0051-CPD-0231
0051-CPD-0232

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SmartLoop Series and is the answer not in the manual?

Questions and answers

Summary of Contents for INIM SmartLoop Series

  • Page 1 EN 54-2 EN 54-4 0051-CPD-0225 0051-CPD-0226 0051-CPD-0227 0051-CPD-0228 0051-CPD-0231 0051-CPD-0232 SmartLoop Analogue fire alarm control panel Installation manual...
  • Page 2: Copyright

    Installation manual Copyright The information contained in this document is the sole property of INIM Electronics s.r.l. No part may be copied without written authorization from INIM Electronics s.r.l. All rights reserved. European directive compliance This control panel has been designed and developed to the highest standards of quality and performance implemented by INIM Electronics s.r.l.
  • Page 3: Table Of Contents

    Installation manual Table of contents Copyright ................2 European directive compliance ..........2 Table of contents..............3 Chapter 1 Introduction................. 5 Application and use 5 Other parts of the system 7 In order to validate the IMQ-SECURITY SYSTEMS certification, and in compliance with EN54-2 regulations: 8 About the SmartLoop fire alarm panel series 8 Description of the models 8...
  • Page 4 Installation manual Alarm relay 33 Fault relay 33 7.10 Connecting devices to the RS485 BUS 33 7.11 Connecting the SmartLoop/NET module 35 7.12 Connecting the SmartLoop/INOUT Board 35 7.13 Connecting to a PC 36 7.14 Connecting a SmartLAN (or SmartLAN/SF) equipped control panel to a PC 37 7.15 Connecting a serial printer 37 7.16...
  • Page 5: Introduction

    Installation manual Chapter 1 Introduction Note: The control panels described in this manual have been designed and developed to the highest standards of quality, reliability and performance. All product components are capable to application requirements and able to operate in compliance with the related technical specifications when the temperature external to their casing complies with Category 3k5 of EN60721-3-3:1995.
  • Page 6 Installation manual [A] Loop All the peripheral devices of the system must be connected in parallel to the loop circuit (2 pole STP). The loop is a closed electrical circuit in which a wide variety of alarm devices can be accommodated. Opening or closing the circuit at any point will generate a fault signal.
  • Page 7: Other Parts Of The System

    Installation manual station. The device can be connected to the control panel loop via an input/output module (not included), installed inside the box, or by means of the RS485 BUS, thus allowing the complete supervision of the power station and control of the 3 outputs. [D] SmartLine-EXT fire-extinction panel (optional) SmartLine-EXT fire-extinction panels are based on SmartLine conventional fire detection panels (4-zones).
  • Page 8: In Order To Validate The Imq-Security Systems Certification, And In Compliance With En54-2 Regulations

    SmartLoop2080/P SmartLoop2080/G SmartLoop2080/S Figure 2 - SmartLoop Series Description of the models The “/P” model is equipped with a keypad, display, fault LEDs, fast buttons and a Zone status LED pad. This model is suitable for locations where extended visual signals and manual control are necessary. This model can be enhanced with the SmartLoop/PRN thermal printer (accessory item).
  • Page 9: Features

    Installation manual The “/G” model is equipped with a keypad, display, fault LEDs and fast buttons and is suitable for installation in locations where visual signals and manual control are necessary. This model can be upgraded at any time after installation (for example, if moved to a location where extended visual signals and manual control are necessary) by replacing its door with a “/P”...
  • Page 10: General Information

    • User Manual The manuals are supplied with the device. For further copies of the Installation Manual, please contact INIM Electronics s.r.l. offices quoting the order number shown in Appendix D - Order Codes. Manual details • Title: SmartLoop Installation Manual •...
  • Page 11: Intellectual Property Rights

    The information contained in this document is private property. All rights reserved No part of this document may be copied or reproduced unless expressly authorized in writing by INIM Electronics, in particular the parts regarding the device specified in paragraph 4.1 Panel.
  • Page 12: Device Identification Details

    - 8.9 Monitored output for remote signalling - 9.5 Points isolation - 9.5 Points isolation - 9.5 Points isolation - 10.0 Test condition Manufacturer: INIM Electronics s.r.l. - 10.0 Test condition - 10.0 Test condition Address: via Fosso Antico, Centobuchi 63076, Monteprandone (AP), Italy Manufacturer: INIM Electronics s.r.l.
  • Page 13: Warranty

    Figure 4 - CE Mark 2.13 Warranty INIM Electronics s.r.l. warrants the original purchaser that for a period of 24 months from the date of final acceptance, the product shall be free of defects in materials and workmanship. The warranty applies only to defects in parts and workmanship relating to normal use.
  • Page 14 Installation manual 1. When removing or handling the boards, hold the board edges only. 2. Do not touch the electronic components, the printed circuits or the metal parts of the connectors. 3. Do not hand the module to another person without first ensuring that you both have the same electrostatic potential.
  • Page 15: Device Management

    Installation manual Chapter 3 Device management Product handling and storage This device is safely packed inside a cardboard box, however, care must be taken to avoid accidental damage during handling. Cartons/boxes should be placed in such a way as to avoid knocks and falls, and special care must be taken to protect the devices from extreme heat and/or cold.
  • Page 16: Technical Description

    The SmartLoop motherboard has a 32 bit microprocessor that controls all the control panel functions, and 2 peripheral microprocessors (one per loop) that manage communications with the system peripherals. INIM’s R & D professionals have developed and designed the SmartLoop motherboard using ground- breaking new generation fire technologies that ensure maximum precision and performance. Deployment of the most advanced reflow technology ensures high-noise immunity and extreme accuracy.
  • Page 17 Installation manual Figure 6 - About the motherboard Connector for the connection with the display board (located on the frontplate) Loop 1 status LED Loop 2 status LED SmartLoop/2L board connector SmartLAN board connector Microprocessor reset button Memory jumper (if removed and the panel is switched Off, the system will restore to factory default settings) Memory battery (3 V lithium battery) RS232 COM connector (DB9 male) USB connector (type B)
  • Page 18: Led Panel

    Installation manual PL and GND terminals for disconnected-battery signalling In the event of primary and secondary power failure (mains and batteries), the PL terminal will connect to GND. Under normal operating circumstances, the PL terminal is disconnected. 24V output for the external power load, protected by a 1.8A self-resettable fuse AUX-R 24V output for external loads, protected by a 1.8A self-resettable fuse (with "Power Cutoff"...
  • Page 19: Technical Specifications

    Installation manual Technical specifications Operating voltage 230 Vac -15% + 10% 50/60Hz Max current draw on AC input 0.9 A @ 230Vac Internal power supply output voltage 27.6 Vdc Internal Power supply MAX current Internal Power Supply output ripple MAX 1% Max current available for the external load (loop devices, external 2.8 A loads, attachment boards, etc.)
  • Page 20 Installation manual Motherboard Loop output terminals Max 0.5 A each loop NAC1, NAC2, NAC3, alarm NAC, fault output 1.3 A MAX Fault relay, alarm relay Voltage-free contact 5A @ 30V max RS485 BUS 1.8 A MAX AUX, AUX-R 1.8 A MAX Current ripple on AUX and AUX-R outputs 1% MAX Normally Open Contact 5A @ 30Vdc MAX...
  • Page 21: Accessory Devices

    Installation manual Chapter 5 Accessory devices Attachment boards The motherboards accommodates the following attachment boards: Figure 7 - The motherboard accessorized with attachment boards Up to 3 SmartLoop/2L loop expansion boards (2080 expandable models only) 1 SmartLoop/NET network board for the creation of a control panel network environment (Hornet technology) 1 SmartLAN LAN board for connection to an Ethernet (Janus technology) 1 SmartLoop/PSTN telephone board for PSTN land line connection...
  • Page 22 Installation manual refer to paragraph Loop 1 status LED 4.2.1 Loop status LED Loop 2 status LED SmartLoop/2L board to board connector (up to 3 boards) Motherboard to SmartLoop/2L board connector Loop 2 Input terminals Loop 2 Output terminals Loop 1 Input terminals Loop 1 Output terminals Screw locations Figure 8 - The SmartLoop/2L board...
  • Page 23 Opera, etc.). This board allows you to carry out remote programming operations (upload/download), manage the system via INIM's SmartLook software application and also manage Dynamic DNS. • SmartLAN/SF – This board allows you to carry out remote programming operations (upload/download), manage the system via INIM's SmartLook software application.
  • Page 24 Installation manual 5.1.4 The SmartLoop/PSTN board The SmartLoop/PSTN board allows the SmartLoop fire control panel to use the land line (PSTN). It manages (and monitors) 2 lines and uses the most widely used reporting protocols (SIA, Contact ID, etc.). It has an 8-slot audio memory for up to eight voice call messages. Completely managed by its on-board microcontroller, it generates emergency calls in the event of a CPU fault, and also any alarm calls triggered during the CPU fault.
  • Page 25: Smartloop/Prn Printer

    Installation manual Green Activity LED Yellow Fault LED (fault on at least 1 of the 6 board channels) Input/Output terminals Interface to motherboard plug (located on the reverse side of the board) Screw locations Figure 13 - The SmartLoop/PSTN board SmartLoop/PRN Printer The SmartLoop/PRN thermal printer module uses 82mm thermal roll paper and can be connected directly to the motherboard (connector cable included).
  • Page 26: The Smartletusee/Lcd And Smartletusee/Led Repeater Panels

    Installation manual The SmartLetUSee/LCD and SmartLetUSee/LED Repeater panels The SmartLoop fire control panel supports 14 SmartLetUSee/LCD remote Repeater panels. These remote panels can be connected to the RS485 bus on the motherboard by means of a 4-pole cable. Repeater panels replicate all the SmartLoop fire system data and allow authorized personnel to access and control the system in accordance with access authorization (access requires code entry).
  • Page 27: Installation

    Installation manual Chapter 6 Installation Danger: Installation of this fire control panel must be carried out in full respect of the local fire codes, laws and bylaws in force, and in accordance with the instructions and guidelines herein. The cable glands must be rated UL94-V1 flame class (or higher) Choosing the mounting location This Fire control panel should be located in a place that is: •...
  • Page 28: Connecting The Smartloop/Prn Printer Module

    Installation manual Connecting attachment boards 6.2.2 Figure 17 - Connecting attachment boards 1. Find the attachment board location on the motherboard (refer to Figure 7 - The motherboard accessorized with attachment boards). If you are installing a SmartLoop/2L board, insert un one end of the flat cable (included) into the respective connector on the motherboard (paragraph 4.2 - [D]).
  • Page 29: Connections

    Installation manual Chapter 7 Connections Note to the Installer regarding wiring and connection compliancy 7.1.1 Two wire connection For a system that is EN54 compliant, no more than 32 sensors can be connected when this type of wiring is used. 7.1.2 Four wire connection For a system that is EN54 compliant, an insulation module must be installed for each group of 32 detectors (refer to...
  • Page 30 Installation manual Note: Each loop output conductor must be fitted with a split ferrite core (included), as shown in the figure below. Figure 18 - Attaching the split ferrite core to loop output cables 7.3.1 Loop terminals LOOP1-O and LOOP2-O - loop output (paragraph 4.2 - [A4] and paragraph 4.2 - [A6]) •...
  • Page 31 Installation manual 7.3.3 Connecting devices to the Loop Il loop wiring can be completed with 2 wires (open loop) or 4 wires (closed loop) using 2 pole STP. Figure 19 - 2 wire connection If you are using a 4 wire connection, connect the STP cable shield to one end of the loop and leave the other end disconnected.
  • Page 32: Nac Outputs (Notification Application Circuit)

    Installation manual NAC Outputs (Notification Application Circuit) 7.4.1 Alarm NAC The ALARM NAC (paragraph 4.2 - [A1]) is a fuse-protected, supervised-silenceable output which is to be connected to the alarm signalling devices. This output will activate when FIRE ALARM conditions are detected. In the event of activation, the output will supply a 24V current in accordance with the polarity indicated on the terminals.
  • Page 33: Aux Output

    Installation manual AUX output The AUX output (paragraph 4.2 - [U]) provides a 24 V (max 1.3 A) power supply output for external loads (ancillary devices). This output is short-circuit protected by a resettable fuse. In the event of a short-circuit, the panel will signal an AUX output fault.
  • Page 34 Installation manual The maximum wire length of the RS485 BUS is 1000 meters. 7.10.1 Setting the devices connected to the RS485 BUS 1. Assign an address to each device. The address identifies the device distinctly on the RS485 BUS. When assigning addresses to repeaters, use the DIP switch (paragraph 5.3 - [C]).
  • Page 35: Connecting The Smartloop/Net Module

    Installation manual 7.11 Connecting the SmartLoop/NET module Use either 4-pole shielded twisted cable for the connections or Cat 5 STP cable for Ethernet connections. The latter will allow you to wire the data communication ring and the emergency alarm ring. Figure 25 - Connecting the SmartLoop/NET module Danger: In order to allow the ring to operate properly, the PORT-B and ALARM-B terminals must be...
  • Page 36: Connecting To A Pc

    If the connection is through the USB port, the system may ask for the installation driver when the USB cable (LINKUSBAB accessory item) is first inserted. The driver is included in the SmartLeague software programme which, once installed, can be found in the following folder: C:\Program files\Inim\SmartLeague\Drivers\ Connections...
  • Page 37: Connecting A Smartlan (Or Smartlan/Sf) Equipped Control Panel To A Pc

    Installation manual 7.14 Connecting a SmartLAN (or SmartLAN/SF) equipped control panel to a PC In this case, the RS232 and USB port will not be available for use. Therefore, the PC must be connected directly to the Ethernet port of the SmartLAN board or through a network switch by means of an inverted patch-cord.
  • Page 38: Connecting The Thermal Probe

    Installation manual Figure 27 - Connecting the batteries 7.17 Connecting the thermal probe Attention: In order to validate the IMQ-SECURITY SYSTEMS certification and comply with EN 54-4 requirements, installation of a thermal probe is essential. This panel has an on-board connector (paragraph 4.2 - [O]) for a thermal probe (accessory item). The ProbeTH thermal probe regulates the battery-charge system by interacting with the battery temperature, this operating method avoids battery damage.
  • Page 39: Connecting The Mains Power Source

    Installation manual 7.18 Connecting the mains power source The power system of the SmartLoop control panel is EN54-4 compliant. Figure 29 - Switching power-supply and mains connection Danger: DO NOT power up the system with a non-compliant voltage (Figure 29 - [B]). 1.
  • Page 40: Powering Up The System

    Installation manual Chapter 8 Powering up the system Attention: When you think you have the system completely wired, double check the integrity of the wiring and ensure that the earth connection has been completed properly before powering Testing wiring integrity Work carefully through the following steps, use a multimeter or similar tool for the electrical measurements.
  • Page 41 Installation manual 7. Once all fault conditions have been cleared, turn the key in the keyswitch to access Level 2 (refer to paragraph 2.4 Operator classification - Access Levels) then press RESET. The display will show: SmartLoop In Service No Alarm No Fault 11/11/11 06:23 Fri Figure 30 - Message on display on first startup...
  • Page 42: Maintenance

    Installation manual Chapter 9 Maintenance The following operations must be carried out regularly. 1. Using a damp lint-free cloth, remove any dust that may have gathered on the control panel enclosure. Attention: Do not use any kind of cleaning product or solvent! 2.
  • Page 43: Troubleshooting

    Installation manual Chapter 10 Troubleshooting 10.1 Fault NAC, alarm or fault output trouble Using a multimeter or similar tool, check the voltage on the terminals. During normal operating conditions (standby status), the measurement should be around 15 V with reverse polarity with regard the silk- screened indications on the terminal board.
  • Page 44: Fault On Devices Connected To The Rs485 Bus

    Installation manual Attention: Ensure that only the system devices are connected to the loop. 10.3 Fault on devices connected to the RS485 BUS Repeater Lost Power Stat. Lost Ext. Stat. Lost If the display shows “ ”, “ ”, “ ”...
  • Page 45 Installation manual • An address has been duplicated, that is, assigned to more than one panel. Access the main menu from the panel. Select Programming, Configuration, View configuration, Network Check the address of each panel in the token-ring network and rectify the error. •...
  • Page 46: Appendix A Enea Devices

    Installation manual Appendix A Enea devices All devices in INIM's new Enea series of addressable-analogue detection devices are LPCB certified and carry the CE mark according to CPD. Each device is equipped with a short-circuit isolator which, in the event of short-circuit between two control-panel (loop) connection wires, is capable of interrupting the negative wire and isolating the wire section concerned.
  • Page 47 From panel: <key>, Programming, <code>, Configuration, Modify Configuration, Manual Configuration, Loop - select the loop - Loop parameters - set the protocol type as INIM and the wiring method as 4 Wire, , Esc, Esc, Esc, Auto Enroll, Loop, place the cursor arrow on the desired loop (column 1 to 8) on the RE-ADDRESS ALL.
  • Page 48 EITK-DRV loop driver). From panel: <key>, Programming, <code>, Configuration, Modify Configuration, Manual Configuration, Loop, select the loop, Loop parameters, set the protocol type as INIM and the wiring method as 4 Wire, , Esc, Esc, Esc, Auto Enroll, Loop, place the cursor arrow on the desired loop (column 1 to 8) on the ENROLL DEVICES line.
  • Page 49: Appendix B Argus Devices

    Installation manual Appendix B Argus Devices Note: The ARGUS devices accepted by this control panel do not have IMQ-SECURITY SYSTEMS certification, refer to the instructions leaflet provided with each device. All Argus Vega devices have built-in loop isolators. Therefore, isolators are not required. A short-circuit on the loop will not provoke loss of any device.
  • Page 50 Installation manual VMCZ100 Conventional-line interface module Interfaces conventional devices to the loop VMIC404 Module with 4 inputs + 4 outputs Module with 4 supervised inputs + 4 outputs (dry contact) VLS100 Intelligent Wall Sounder Loop-powered sounder (wall mount) VWLS100 Weatherproof Intelligent Wall Sounder Loop-powered sounder for outdoor installation VLS100-AV Intelligent Wall Sounderflasher...
  • Page 51 Installation manual Device Consumption Device in stand-by in alarm 90 PA Detectors 6 mA 120 PA Modules 6 mA Configuring Argus devices Every ARGUS device requires an address to identify it in the loop. You can address ARGUS devices by either using a VPU (Vega Programming Unit) or by means of the Auto-addressing option.
  • Page 52 Installation manual 2. Fit the detector into the VPU100 (twist on). 3. Press any button on the VPU100 to switch On the unit. 4. Using the scroll keys, select an address (1-240) then press the “WRITE” button (top left) to confirm the selection.
  • Page 53: Appendix C Apollo Devices

    Installation manual Appendix C Apollo Devices Note: The APOLLO devices accepted by this control panel do not have IMQ-SECURITY SYSTEMS certification, refer to the instructions leaflet provided with each device. Apollo devices are not equipped with built-in loop isolators (that is, unless otherwise specified). Therefore, you must install loop isolators in such way as to avoid the loss of devices in the event of short-circuit.
  • Page 54 Installation manual 59000-407 Sounder Heat detector Heat detector with sounder base 59000-415 Heat detector High temperature heat detector with standard base 59000-416 LED heat detector High temperature heat detector with LED driver base 59000-417 Sounder Heat detector High temperature heat detector with base sounder 59000-605 Smoke detector Optical smoke detector with standard base...
  • Page 55 Installation manual Modules Model Name Description 55000-809 XP95 Switch monitor plus Module with 1 input with delay and reset output for waterflow detectors (waterflow alarm) 55000-810 XP95 Switch monitor Single input module 55000-813 XP95 Zone monitor Conventional detector interface module 55000-818 XP95 Input/Output module Module with 1 relay output + 1 supervised input + 1 non-...
  • Page 56 Installation manual 1. Remove the detector from its base (twist off). 2. Using a flat-bladed screwdriver or similar tool, push the locking tab and slide the Xpert card out of its holder. 3. Using a flat-bladed screwdriver or similar tool, remove the pips in such way as to assign an address to the Xpert card (refer to the Address Table in the device instructions).
  • Page 57: Appendix D Order Codes

    Installation manual Appendix D Order Codes Following are the order codes of INIM Electronics s.r.l. products: Code Description DCMIINE0SLOOP Installation Manual DCMPINE0SLOOP Programming Manual DCMUINE0SLOOP User Manual IPS24140 Switching Power supply/Battery 4A@27.6Vdc Link232F9F9 RS232 link LinkUSBAB USB cable for PC to INIM device connection...
  • Page 58: Appendix D Notes

    Installation manual Notes: Notes:...
  • Page 59 Installation manual...
  • Page 60 Fosso Antico Loc. Centobuchi 63076 Monteprandone (AP) ITALY Tel. +39 0735 705007 _ Fax +39 0735 704912 info@inim.biz _ www.inim.biz DCMIINE0SLOOP-R302-20120418...

Table of Contents

Save PDF