2. Commissioning
Festo P.BE−CDVI−DN−EN en 0404NH
Fault Action, Main Unit Extension" parameter
The same function as above with Main Unit", but for the
output module in the extension.
Fault Value, Main Unit Extension"
The same function as above with Main Unit", but for the
output module in the extension.
Reaction of the outputs in the Idle mode
The Idle mode is assumed by the slaves when this is re
quested by the master or the scanner. The following applies
in this example:
Inputs are transferred
Outputs of the slaves are no longer updated
In the idle mode, the outputs for valve control and for the
output module can assume one of the following states:
Reset the output
Set the output
Freeze the current status of the output
The state to be assumed can be determined separately for
each output. The standard setting is Reset output".
The valves of the CDVI−DN and the outputs of the modules in
the CP extension are set with separate parameters:
2−21