2. Commissioning
2−20
The valves of the CDVI−DN and the outputs of the modules in
the CP extension are set with separate parameters:
Fault Action, Main Unit" parameter
With this parameter you can define for each output whether it
is to freeze the current status in fault mode or whether it is to
assume a certain output status (0/1).
Parameter value
0
1
Tab. 2/2:
Fault Value, Main Unit" parameter
With this parameter you can define for each output the out
put status (0 or 1) which it is to assume in the fault mode.
Parameter value
0
1
Tab. 2/3:
The set parameter value will only be taken into account if the
relevant output is set to 0 in the Fault Action parameter.
Meaning
The output will be set to a certain output
status (0 or 1). The output status is defined
with the parameter Fault Value, Main Unit".
The status of the output is frozen.
Meaning
Output is reset
Output is set
Festo P.BE−CDVI−DN−EN en 0404NH