3.4.16
Control module «universal» E3G070
Pos.
Component
1
DIL switch S3
I-Bus address
2
Maintenance switch S2
Activate test LEDs
3
Jumpers X12/13 and Y12/13
Program transmission alarm/fault
4
Jumper X60
Ground short monitoring unit
For notes on ground short monitoring
Õ see page 103
3.4.17

Remote transmission interface E3G091 (supersedes E3G090)

Pos.
Component
1
Jumpers X1/Y1 to X6/Y6
Define make and break contacts
Fire & Security Products
Siemens Building Technologies Group
Set according to system documentation
Set to ON for commissioning
Resolder if necessary (according to system
documentation)
Connect up contacts if ground short moni-
toring unit is to be activated
Test LEDs
2
Resolder if necessary (according to system
documentation)
Preparation
4
1
Preparation
1
Default
address 0
Set to OFF
On X13 and Y12
Open (monitoring unit
inactive)
3
Default
All jumpers in pos. X
15