4.10.4

Control unit CI1142 and terminal CT1142

74
Fire & Security Products
Siemens Building Technologies Group
Procedure
Connect the maintenance PC serial interfaces (COM1) to the CI11 main control
unit/CT11 terminal (connector ST2 on B3Qxxx) via the modem box Z3W050/51 +
adapter box B3D040 or via the modem box B3D021.
Start the SWE11
Load configuration data for CI11 control unit/CT11 terminal
Õ Ensure C-Bus address is correct!
Start transfer of configuration data from the SWE11
Õ Function Comm. Õ Fast Download –> CS11 (only with modem box B3D021) or
Õ Function Comm. Õ Download CS11
If there is not enough available memory (RAM) on the control unit/terminal, the mes-
sage 'No data base memory available' appears on the SWE11 information line. In such
cases, refer to page 81.
After a successful download the following message appears in the SWE11: 'Operation
successful'
Once the startup procedure on the control unit/terminal has been completed, the 'Sys-
tem operation' LED lights up
CI/CT11
RS232 interface:
connector ST2 on
B3Qxxx
É
É
Adapter B3D040 + Z3W050/51
or
modem box B3D021
Configuration data of the
station CI/CT11 loaded
É É É É
Serial interface
(COM1)
SWE11
e1249d 3
01.1999