Trouble message on the terminal: 'C-Bus ASIC or RAM'

C-Bus ASIC or RAM on the master module (E3X1xx) or
the control console (B3Qxxx) faulty.
A new EPROM version has been used
(e. g. Upgrade 5.13 → 5.14).
6.1.11

Trouble message on terminal: 'Short circuit or open line'

Short circuit or break on an interactive, AnalogPLUS or
MS9i detector line (D-Bus)
Fire & Security Products
Siemens Building Technologies Group
Trouble
Trouble
see also AnalogPLUS – Trouble shooting section 6.2
– If the RAM modules are not pushed fully home in the
slots, rectify.
or
– Replace RAM modules
or
– Replace corresponding module (E3X1xx or B3Qxxx)
Carry out new download!
– Rectify short circuit or break and reconfigure relevant
line module (function 'RECONFIGURE D-Bus')
Remedy
Remedy