Address allocation for AnalogPLUS and MS9i devices

(according to order of installation)
Line 1
AnalogPLUS detector
Loop or stub line
Line 2
AnalogPLUS detector
Loop or stub line
Installation layout:
14
58
Fire & Security Products
Siemens Building Technologies Group
Principle
The devices in the physical structure are allocated consecutive D-Bus addresses on the
detector bus according to the order of installation.
Allocation of addresses can take place at the time of generation of the data file in
AlgoWorks. The fire detection system does not have to exist for that purpose.
The installation plans for the system act as the reference for the order of installation on
the D-Bus.
Example: AnalogPlus detector bus
E3M110/111
Terminal block
F1
F2
F3
If loop line:
F4
return
F5
F6
3
1
2
DT
DT
12
13
11
DO
DO
Procedure
1. Set up the physical structure according to the order of installation, or in an existing
physical structure, sort the devices according to the order of installation:
ÕFunction Special Õ Mark
ÕFunction Structure Õ Move
2. Arrange CSX numbers in ascending order
ÕFunction Special Õ Renumber CSX
3. Set the D-Bus addresses according to the CSX numbers.
ÕFunction Loc. Õ Set Bus addr. = CSX
D-Bus address 1
D-Bus address 2
X10
+
1
2
+
3
4
+
5
6
4
5
DO
DO
DO
9
DO
DT
10
DT
DO
...
6
DO
8
DO
7
DO
e1249d 3
01.1999