7.7
Activation of interactive and AnalogPLUS devices
7.7.1
Automatic detectors
OptoRex
Detector exchanger/tester DZ1193 or
WaveRex
Lamp STABEX (in explosion-hazard areas)
7.7.2
Manual call points
– Insert test key
– Wait until the response in-
dicator flashes
– Remove test key again
Test key
Version «KAC»
Fire & Security Products
Siemens Building Technologies Group
DZ1193
detector tester RE6 + DZZ1190
approx.
50mm
Lamp LE3 or
PolyRex
RE6
Sensor B
Response indicator
Sensor A
– Open front of the manual
call point with the key
– Push button
– Wait until the response in-
dicator flashes
– Close the front
Version «DIN»
ThermoRex
Detector tester RE6T
– Open the front of the
manual call point with the
key Õ manual call point is
activated
– Wait until the response in-
dicator flashes
– Close the front
Version «EN»