Text Control Terminal B3Q590 - Siemens Cerberus CS1140 Commissioning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

3.4.21

Text control terminal B3Q590

Pos.
Component
1
DIL switch S3
LON-Bus address
2
Resistor R1
LON-Bus termination (EOL)
3
Labels
Included in Z5B....
4
KABA key-operated switch
(optional)
Included in Z3S100
Afterwards fit B3Q590 and connect up LON-Bus and supply cables and LED control unit if necessary
Fire & Security Products
Siemens Building Technologies Group
Set as per system documentation
R1 must be removed if B3Q590 is not the
last device on the LON-Bus (when wired as
a stub line)
Õ see also description of hardware
(document e1260)
Attach additional labels if necessary and in-
sert
Remove existing lock barrel and fit KABA
barrel
3
4
Preparation
3
2
Default
address 0
100W
Supplied/ordered sepa-
rately (not available in
all countries)
Nordic fire brigade key-
operated switch fitted
1
19
e1249d 1
01.1999

Hide quick links:

Advertisement

Table of Contents
loading