Trouble Message In Swe11: 'No Data Base Memory Available; Trouble Message On Downloading (In Swe11): 'Incompatible File Version; Trouble Message On Terminal: 'Control Unit Configuration - Siemens Cerberus CS1140 Commissioning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

6.1.6

Trouble message in SWE11: 'No data base memory available'

Not enough available memory on the RAM modules on
the main control unit
6.1.7

Trouble message on downloading (in SWE11): 'Incompatible file version'

The data file (system configuration) on the SWE11 and
the CC/CI/CT program (on the EPROM) are not compat-
ible
6.1.8

Trouble message on terminal: 'Control unit configuration'

Õ Configuration error (after download SWE11 Õ CC/CI11)
There is at least one device in the physical structure
which has not yet been localized
Õ If none of the as yet unlocalized devices is linked to a
logical element, only the trouble message 'Control
unit configuration' appears
Õ The element REFERENCE message '... IMPAIRED'
appears for every unlocalized device that is already
linked to a logical element
Collective line (E3M080):
– the parameter 'line no.' of a collective line (device
'DE DS11 line') is = 0
AnalogPLUS line (E3M11x):
– The parameter 'line no.' of a line = 0
Fire & Security Products
Siemens Building Technologies Group
Trouble
Trouble
Trouble
– EP5 only supports "large" RAM modules (Z3S070). If
this is inadequate an additional CC11 or CI11 station
is required
Action to be taken: Either install a program version that
is compatible with the data file, or convert the data file to
make it compatible with the program version in use
ÕAfterwards, perform download
The versions in use can be ascertained as follows (Õ
page 72):
– The data file version is listed in the station directory of
– The data file version is listed in the station directory of
the SWE11
– The CC/CI/CT program version is printed on the
EPROMs
– At the start of the download procedure, the version
number of the connected station is displayed on the
SWE11 information line
Example: 'Downloading to station type CCQ00514'
– localize all logical elements / physical devices
or
– do not enter physical devices and link to logical ele-
ments before the localization is also carried out
– the value of the field 'line no.' may not be 0 (valid val-
ues: 1..8)
Õ Set value accordingly and once again load the config-
uration into the CC/CI11 control unit
(Comm. Õ Fast Download –> CS11)
– the value of the field 'line no.' may not be 0 (valid val-
ues: 1..4)
Õ Set value accordingly and once again load the config-
uration into the CC/CI11 control unit
(Comm. Õ Fast Download –> CS11)
Remedy
Remedy
Remedy
81
e1249d 4
01.1999