5
Exchange of hardware
5.1
CPU cards
5.2
I-Bus cards
5.3
E-Bus cards
5.4
Interactive devices
76
Fire & Security Products
Siemens Building Technologies Group
If a CPU card for a CC1142 (E3X10x), CI1142 (B3Qxxx), CI1145 (E3X120) control unit or
a CT1142 (B3Qxxx) terminal is replaced, the following operations must be carried out:
Disconnect control unit/terminal from power supply
Replace the CPU card, reconnect all cables
Re-adjust all switches and jumpers
Reconnect power
Repeat download of configuration data
If an I-Bus card (E3Mxxx, E3Lxxx, E3Gxxx, ...) is replaced, the following operations must
be carried out:
Disconnect control unit from power supply
Replace the I-Bus card, reconnect all cables
Õ set the correct I-Bus address !
Reconnect power
Õ Configuration data does not need to be downloaded again
If an E-Bus card (K3M071, K3M111, K3M080, ...) is replaced, the following operations
must be carried out:
Disconnect control unit from power supply
Replace E-Bus card, reconnect all cables
Õ Note the mounting space
Reconnect power
Õ Configuration data does not need to be downloaded again
Automatic detectors can be replaced without localization having to be repeated pro-
viding the type is not changed The following operations must be carried out:
Remove the old detector from the base
Insert new detector (line does not have to be disconnected from power supply)
Õ As long as the new detector type is the same as the old detector type, the system
reconfigures itself automatically
Õ If a different detector type is purposely installed, a change in the configuration is nec-
essary:
Change the device type accordingly in the physical structure
Download the updated configuration data to the control unit
Õ If the ID module of a base or the whole base is replaced, the configuration must be
modified as follows:
In the physical structure, set the D-Bus address of the replaced device to 0 (using
raw data editor)
Repeat localization and assignment procedure for the device concerned
e1249d 3