Collective Devices - Siemens Cerberus CS1140 Commissioning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

5.7

Collective devices

78
Fire & Security Products
Siemens Building Technologies Group
The following operations must be carried out:
If manual call points are to be replaced, disconnect line from power supply
Remove old detectors from their bases or unmount manual call points
Insert new detectors or mount manual call points
Reconnect line to power supply (if disconnected)
Õ As long as the new detector type is the same as the set line type for the collective line,
the system reconfigures itself automatically
Õ If the new detector type does not correspond to the set line type of the collective line,
a change in the configuration is required:
Change the line type accordingly in the physical structure
Download the updated configuration data to the control unit
e1249d 3
01.1999