Siemens Cerberus CS1140 Commissioning page 65

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

Fire & Security Products
Siemens Building Technologies Group
Output module DC1136
The output module DC1136 consists of a digital output section and a digital input section,
each of which occupies its own D-Bus address.
The output section always occupies the lower of the two immediately consecutive D-Bus
addresses.
DC1136 as output element with confirmation
Normally, this module is linked with the module with the element type 'output element with
confirmation' ('EL out 2'). Other links should only be used in exceptional circumstances.
Example: DC1136 as 'output element with confirmation'
Addr. 1
E3M110/111
DC1136 as output element without confirmation
ü
Use only in exceptional circumstances!
Even if the input section of the module is not used, it still occupies two D-Bus addresses.
In the physical structure, an output section (DC1136o) and an input section (DC1136i)
must be created but only the output section (DC1136o) is linked to the logical structure.
The output section always occupies the lower D-Bus address in this case too.
DC1136
2
3
(DC1136o)
(DC1136i)
Output
switch
4
5
6
Con-
firmation
e1249d 3
01.1999
61