Preparation of hardware

4
Preparation of hardware
4.1

Control module 'Extinguishing' E3G080

Pos.
Component
1
Programming switch 'S3': I-Bus address
Programming switch 'S2': Determine emergen-
2
cy operation concept
3
Resistors 'R60/61'
4
Maintenance switch 'S1': Test to block all
outputs, without real activation (activation
test LEDs 'H1'....'H4')
5
Maintenance switch 'S4': For initialization of
commissioning functions
6
Jumper 'X2': Ground fault monitoring 'LON-
Bus'
7
µP 'D2'
8
Connection level
4.2

Additional outputs

Building Technologies
Fire Safety
Preparation
set according to system documentation
set according to system documentation
S2-1/2 > 'OFF' = no function if µP E3G080 mal-
functions
-> see also description in document 001260
Activating device 1 is between 16...160 :
> Remove 'R60' (71K5)
Activating device 2 is between 16...160 :
> Remove 'R60' (71K5 )
set to 'ON', so that when switching on for the first
time, all outputs are blocked (meaning of the LEDs
see chapter 5.2)
only effective if switch 'S1' is set to 'ON'
-> description see chapter 5.2
Ground fault monitoring -> see also in document
004594
set as described in document 001260, chapter
'Ground fault monitoring'
check version, see Release notes docu 004767
check that all peripheral equipment planned is
connected (according to system documentation)
3
1
S3
D2
S1
4
S2
5
S4
2
In accordance with the standard EN12094, the outputs
Extinguishing actuated
Extnguishing fault
Extinguishing blocked (optional)
Extinguishing agent mech. blocked (optional)
are made available by means of a separate control plug in module (e.g. E3G060,
see document no. 1260) or I/O module (e.g. FDCIO222, see document no.
007023).
R61
R60
R151
X2
6
7
Default
Address 0
all switches to on 'ON'
'R60/61' inserted
> for activating device
161....320
set to 'OFF'
removed (inactive)
inserted
8
009853_b_en_--
01.2013
11