4.5.4

Manual allocation of AnalogPLUS devices (with address allocation)

Important Restrictions for the AnalogPLUS System:
G As soon as at least 1 device has been allocated after uploading, all devices present in the localization structure
must also be allocated.
G On completion of allocation, the configuration must always be downloaded to the control unit.
G If the system is extended using address allocation the address allocation of the element type 'output element
with confirmation' ('EL out 2') must be carried out manually.
Automatic detectors and manual call points
select
AlgoWorks 00ST0245
09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB
(1801,1)
001.001/SE fire/2nd floor west
001.001.001/ZO single/1/laboratory 201
>001.001.001.001/001: DO1131
4
>001.001.001.002/001: DO1131
2 AI
>001.001.001.003/001: DO1131
>001.001.001.004/001: DO1131
001.001.002/ZO multi/2/laboratory 203
>001.001.002.001/004: DOT1131
6 Window
>001.001.002.002/004: DOT1131
5 Door
Logic element, physical de-
vice (not visible at the mo-
ment) and device in the local-
ization structure are identified
as located
Õ no prefix
Fire & Security Products
Siemens Building Technologies Group
Procedure(with a DO1131 automatic detector as an example)
1. Switch over from the physical structure to the localization structure
Õ Function Loc. Õ Commissioning
2. Using the commissioning list, select an automatic detector or manual call point in the
localization structure and the corresponding element in the logical structure
Reference:
Localization index of the address allocation
(1701,425)
(1601,426)
(1501,427)
(1501,428)
(1501,429)
(1501,430)
(1602,445)
(1501,446)
(1501,447)
3. Link nodes together
Õ Function Structure Õ Link