4.4

Localization of AnalogPLUS devices

Note:
Whenever possible, commissioning should be carried out in the order of installation, especially if the modules
DC1135 or DC1136 are used (Õ see page 58).
4.4.1

Overview of localization methods

4.4.2

Basic requirements and restrictions

34
Fire & Security Products
Siemens Building Technologies Group
Localization by address allocation
Activate localization mode
Address allocation by
insertion
Insert detectors in any order
(activate manual call points,
insert input / output module
electronics) and enter se-
quence in the commissioning
list / ground plan or register
the inserted / activated de-
vices with the SmartHandy
Deactivate localization mode, upload localiza-
tion data from the control unit into SWE11.
Using the SWE11, allocate the devices of the
localization structure to the corresponding
elements of the logical structure; use Smart-
Handy data where possible
After uploading the localization structure: As soon as one device is allocated, all the
others must also be allocated and the configuration must be downloaded before other
devices can be localized.
During address allocation only devices which have not yet been localized and allocated
in the control unit can be inserted and activated.
During address allocation no devices may be removed (A defective detector can be
exchanged immediately at any time).
All devices must be able to respond from the beginning of the line (outgoing circuit of the
D-Bus).
Before beginning address allocation, all devices already localized must be inserted.
Ensure that during address allocation, no external signals (door contacts, ...) are ap-
plied to the inputs of DC1131 input modules.
Address allocation by
activation
Activate devices in any or-
der and enter sequence in
commissioning list /
ground plan or register the
activated devices with the
SmartHandy
e1249d 2
01.1999