Led Module Fto2008-A1; Fba Terminal Fto2004-C1 [Ch]; Floor Repeater Terminal Ft2010 And Floor Repeater Display Ft2011 - Siemens FS20 Planning Manual

Fire detection system
Table of Contents

Advertisement

5.6 LED module FTO2008-A1

1
2
(1) LED red/green
(2) LED yellow
(3) Inscribable fields

5.7 FBA terminal FTO2004-C1 [CH]

5.8 Floor repeater terminal FT2010 and floor repeater
Building Technologies
Fire Safety
The LED module FTO2008-A1 contains 24 indicator zones. Each ↑ zone
contains one red / green bicolor LED and one yellow LED.
Any events can be assigned to the LEDs. Each LED may be configured as a
static or flashing indicator. Normally the LED indicator is used as a zone
indicator.
The LED module is connected to the station-internal bus and can be cascaded
to up to a maximum of five LED modules.
The LED module is not individually available as an option. It is permanently
integrated in the following components:
Operating unit (+LED indicator) FCM2037-A2
3
Operating add-on (2x LED indicators) FCM2038-A2
Operating add-on (4x LED indicators) FCM2036-A2
The operating units and operating add-ons are permanently integrated
depending on the station type. The number of indicator zones required
determines which ↑ station must be ordered.
Standardized fire brigade operating and indicator panel according to Swiss
standards. The FBA terminal is pre-installed in the corresponding operating unit.
The FBA terminal is connected to the station-internal bus.
The FBA terminal is not individually available as an option. It may be permanently
built-in, depending on the station type.
display FT2011
↑ Floor repeater terminal FT2010
Project planning of indication and operation devices
LED module FTO2008-A1
↑ Floor repeater display FT2011
5
43 | 242
008843_v_en_--
2015-12-15

Advertisement