Siemens Cerberus CS1140 Commissioning page 49

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

Select DC1154
Select 1st element
AlgoWorks 00ST0245
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB
(1801,1)
001.001/SE fire/2nd floor west
001.001.001/ZO single/1/laboratory 201
>001.001.001.001/001: DO1151
4
>001.001.001.002/001: DO1151
2 AI
>001.001.001.003/001: DO1151
>001.001.001.004/001: DO1151
001.001.002/ZO multi/2/laboratory 203
>001.001.002.001/004: DOT1151
6 Window
>001.001.002.002/004: DOT1151
5 Door
AlgoWorks 00ST0245
09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB
(1801,1)
001.001/SE fire/2nd floor west
001.001.001/ZO single/1/laboratory 201
>001.001.001.001/001: DO1151
4
>001.001.001.002/001: DO1151
2 AI
>001.001.001.003/001: DO1151
>001.001.001.004/001: DO1151
001.001.002/ZO multi/2/laboratory 203
>001.001.002.001/004: DOT1151
6 Window
>001.001.002.002/004: DOT1151
5 Door
Fire & Security Products
Siemens Building Technologies Group
Reference:
Localization index of the address allocation or
device identification
09–APR–1997, 14:42
(1701,425)
(1601,426)
(1501,427)
(1501,428)
(1501,429)
(1501,430)
(1602,445)
(1501,446)
(1501,447)
3. Link nodes together
Õ Function Structure Õ Link
CAUTION:
Because input and output sections of a DC1154 are represented as two individual
devices in the physical structure and no common reference is available showing affil-
iation to the same DC1154, the SWE11 cannot automatically transfer the localization
data to both devices. The localization data must, therefore, be allocated individually
to both elements linked to the physical devices .
After the first linking with an element, the DC1154 is identified as localized Õ no pre-
fix.
4. Using the commissioning list, select the second element corresponding to the
DC1154 in the logical structure
Reference:
Localization index of the address allocation or
device identification
(1701,425)
(1601,426)
(1501,427)
(1501,428)
(1501,429)
(1501,430)
(1602,445)
(1501,446)
(1501,447)
Select second element
5. Link nodes together
Õ Function Structure Õ Link
Procedure if the input section or output section of the same DC1154 is used only
after commissioning has already been carried out
1. According to application, generate and link a new or (with Replace) modified logical
element and a new physical device
2. In the physical structure, open nodes of the device already in operation
3. Note D-Bus address and device ID
4. Enter the above value in the newly generated device
Select DC1154
Õ identified as localized, because
an element has already been allo-
cated !
45