Trouble message in SWE11: 'Nodes are not localizable Õ check node types'
Õ Localization data can not be allocated
The logical element, to which the localization data
should be allocated, is not linked to a physical device
Õ the logical element is identified with a '*' prefix
The logical element, to which the localization data
should be allocated, is linked to a physical device of
another function unit
The logical element, to which the localization data
should be allocated, has already been localized
Õ The logical element has no prefix
The device type in the physical structure does not match
that in the localization structure
I-Bus address, line no. or type of function unit in the
physical structure and localization structure do not
match
6.1.5

SWE11: Prefix '?' for a node in the localization structure

Õ The device localization data is invalid
Contact difficulties during 'address allocation by inser-
tion'
Production fault (device is defective)
ID module in the base is missing (only required for inter-
active automatic detectors)
ID module in the base is defective
(only present on interactive automatic detectors)
ID module contacts are bent (only possible on interac-
tive automatic detectors without designation ...A)
Communication fault on the detector bus
Õ Unlikely if other devices have been correctly localized
on the same detector bus
80
Fire & Security Products
Siemens Building Technologies Group
Trouble
Trouble
Link the logical element to a physical device and repeat
allocation of the localization data
Õ Make sure device types are compatible
Link the logical element to a physical device on the cor-
rect line and repeat allocation of localization data
Using the commissioning list, check to see if the correct
logical element is selected
– Correct element selected:
The wrong localization data has been allocated at
some previous point
Õ Cancel incorrect element localization and repeat
allocation of localization data
– incorrect element selected:
Õ Select the correct element and repeat allocation of
localization data
Either alter the device type in the physical structure or
replace the device and re-localize
Alter I-Bus address, line no. or relevant function unit
type in the physical structure
Repeat localization procedure for this location using 'ad-
dress allocation by activation'
Replace device
– Insert ID module in base
– Repeat localization procedure for this location
– Replace ID module
– Repeat localization procedure for this location
– Straighten contacts or replace ID module
– Repeat localization procedure for this location
– Check detector leads
– Repeat localization process for this location