'Collective' input module DC1151
select
AlgoWorks 00ST0245
09–APR–1997, 14:42
File: C:\AWDATA\DEMO_VPB\DCR001L1.TXT
Listing of the logical structure (26447,19533,31046)
–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
001/AR/demo system VPB
(1801,1)
001.001/SE fire/2nd floor west
001.001.001/ZO single/1/laboratory 201
>001.001.001.001/001: DO1151
4
>001.001.001.002/001: DO1151
2 AI
>001.001.001.003/001: DO1151
>001.001.001.004/001: DO1151
001.001.002/ZO multi/2/laboratory 203
>001.001.002.001/004: DOT1151
6 Window
>001.001.002.002/004: DOT1151
5 Door
Output module DC1154/DC1154-AA
42
Fire & Security Products
Siemens Building Technologies Group
Procedure
1. Switch over from the physical structure to the localization structure
Õ Function Loc. Õ Commissioning
2. Using the commissioning list, select a DC1151 input module in the localization struc-
ture and the corresponding element in the logical structure
Permissible element types:
– Collective detector element 1 ('EL col. det. 1')
– Collective detector element 2 ('EL col. det. 2')
– Collective detector element 3 ('EL col. det. 3')
– Collective manual call point element ('EL DS11c/MS9i man')
Reference:
Localization index of address allocation or
device identification
3. Link nodes together
Õ Function Structure Õ Link
(1701,425)
(1601,426)
(1501,427)
(1501,428)
(1501,429)
(1501,430)
(1602,445)
(1501,446)
(1501,447)
Possible Uses
The output module DC1154 consists of a digital output section and a digital input section.
These may be used independently of one another. In the physical structure they are rep-
resented as individual devices on an interactive line ('out' and 'in'). Depending on the ap-
plication, the two physical devices are linked with the same or two different logical ele-
ments.
Procedure to be adopted if the input section is used as confirmation path for out-
put section
ü
Normal situation
ü
Element type to be used: 'Output element with confirmation path ('EL out 2')
e1249d 2