Power Synchronized Unit; Figure 175 Power Distribution Unit (Ac24A/200V, 2U, 16 Outlets); Table 97 Power Distribution Unit (Ac24A/200V, 2U, 16 Outlets) And Provided Power Cord Specifications - Fujitsu ETERNUS DX S5 Series Design Manual

Hybrid
Hide thumbs Also See for ETERNUS DX S5 Series:
Table of Contents

Advertisement

6. Hardware Configurations

Power Synchronized Unit

Power Distribution Unit (AC24A/200V, 2U, 16 Outlets)
There are 16 outlets.
Figure 175
Power Distribution Unit (AC24A/200V, 2U, 16 Outlets)
1
Main line switch
This turns on and off the power distribution unit.
2
Outlet (OUTPUT)
This is a socket (IEC60320 C13) for outgoing power supply. This socket is used to connect a power cord (AC
output cable).
The specifications of a power distribution unit and the power cords that are provided are shown below.
Table 97
Power Distribution Unit (AC24A/200V, 2U, 16 Outlets) and Provided Power Cord Specifications
Item
Power
Input cable
Power Synchronized Unit
A power synchronized unit detects changes in the AC power output of the Uninterruptible Power Supply (UPS)
unit that is connected to the server and automatically turns on and off the ETERNUS DX.
For more details about power synchronized units, refer to "Configuration Guide (Power Synchronized Unit)".
1
1
Voltage
Phase
Frequency
Connection type
Length
Quantity
2
Specifications
AC 200 – 240V
Single
50Hz/60Hz
Straight-through n NEMA L6-30P
4m
2