2. Commissioning
2.2.4 Assignment of input/output addresses of the CP system
to A-B I/O addresses
In the following example the CP system has field bus
address 4.
CP FB8 9809a
I or O address
Input and output
addresses of CP system
0 ... 7
8 ... 15
16 ... 23
24 ... 31
32 ... 39
40 ... 47
48 ... 55
56 ... 63
A-B designation
e.g. set address 4
010/00 ... 010/07
010/10 ... 010/17
011/00 ... 011/07
011/10 ... 011/17
012/00 ... 012/07
012/10 ... 012/17
013/00 ... 013/07
013/10 ... 013/17
2-7