5 Application functions List of Parameters

In this section there are the application parameter list. The list are in the same order of menu and parameter
list of the alphanumerical keypad in PID IMM application menu.

5.1 Configuration menu

PID_IMM Application can be configured by parameters included in SERVOPUMP PID \ CONFIGURATION
menu. This is the first sub-menu in the PID_IMM main menu.
During basic motor startup, speed control without P/Q regulation is possible by setting parameter Ipa 11000
Control Selector to "SPEED"; for pressure / flow regulation.
Control Selector will have to be set to "ADP200" starting from Version 1.0.0 with PID IMM application version
1_x37_0 (Standard P+S is the old application)
In CONFIGURATION menu user has the possibility to make the proper selection for control and general
settings.
Here the explanation of the parameter then the parameter list of Configuration Menù.
Control Selector
MasterSlave
Nominal pump speed (rpm): it is used to scale the speed reference signal from PLC.
As default the speed reference must be sent to drive with signal from 0 to 10V. 0V is
interpreted as 0 rpm, 10 V means Nominal pump speed
Nominal Pump pressure (bar): it is used to scale the pressure reference signal from PLC.
As default, pressure reference must be sent to drive with signal from 0 to 10V. 0V is
interpreted as 0 bar, 10V means Nominal pump pressure
Full Scale Press Sens (bar):
Full scale sensor pressure is used to scale the pressure feedback signal from pressure
transducer. As default, pressure reference must be sent to drive with signal from 0 to 10V.
0V is interpreted as 0 bar, 10V means Full scale pressure sensor
Analog pressure sensor gain (-):
Gain applied on pressure feedback signal. This parameter can be used to adjust tolerance
on pressure sensor. Factory and suggested initial value is 1.0.
Note!
Positive or negative is just conventional.
This parameter must be set carefully. A wrong setting of this parameter can lead to pump damaging.
ADP200 Application PID-IMM
This parameter allows the use to Set the application control type.
1=SPEED: In this case control will follow the speed reference only. If actual pressure
feedback is over the pressure set-point, the application will stop the motor and
trigger an "Over Pressure" alarm.
drive commissioning check the pump correct direction and speed loop tuning.
2=ADP200: Standard control for the application. The control will manage both
pressure and speed control.
This configuration of the drive for multi-pump. It can be:
0=Master: The drive is working alone or as Master
1=Slave: Convergent mode
2=SlaveDivMaster: Drive will work as Slave in Convergent mode and as Master for
the divergent slaves pump
3=SlaveDivSlave: Drive will work as Slave of Master in Convergent mode and Slave
of the SlaveDivMaster in Divergent Mode
This function can be used for motor and
User Manual
Pag. 40 of 80